ICS: |
29.260.20
|
|
||||||||
|
جميع الحقوق محفوظة لهيئة لتقييس لدول مجلس التعاون لدول الخليج العربية.
ما لم ينص على خلاف ذلك، لا يجوز إعادة إنتاج أي جزء من هذا المنشور أو استخدامه بأي شكل آخر أو بأي وسيلة، إلكترونية أو ميكانيكية، بما في ذلك التصوير، أو النشر على الإنترنت أو الإنترانت، دون إذن كتابي مسبق من هيئة التقييس لدول مجلس التعاون لدول الخليج العربية على العنوان أدناه أو الدول الأعضاء في الهيئة داخل بلدانهم.
|
||||||||
|
All rights reserved to GCC Standardization Organization (GSO). Unless otherwise specified, no part of this publication may be reproduced or utilized otherwise in any form or by any means, electronic or mechanical, including photocopying, or posting on the internet or an intranet, without prior written permission. Permission can be requested from either GSO at the address below or GSO's member body in the country of the requester.
|
||||||||
|
Outreach Dept, Knowledge Management Section
GCC Standardization Organization (GSO)
P.O.Box: 85245 Riyadh 12511
Kingdom of Saudi Arabia
|
إدارة التواصل، قسم إدارة المعرفة
هيئة التقييس لدول مجلس التعاون لدول الخليج العربية (GSO)
ص. ب: 85245 الرياض 12511
المملكة العربية السعودية
|
|||||||
| Tel: | +966115208000 | :هاتف | ||||||
| Fax: | +966115208010 | :فاكس | ||||||
| E-Mail: | csc@gso.org.sa | :بريد إلكتروني | ||||||
| Website: | www.gso.org.sa | :موقع ويب | ||||||
| تقديم خليجي |

| IEC 60079-0 |
INTERNATIONAL STANDARD | Edition 7.0 2017-12 | |
| Explosive atmospheres – Part 0: Equipment – General requirements | ||
![]() | THIS PUBLICATION IS COPYRIGHT PROTECTEDCopyright © 2017 IEC, Geneva, Switzerland |
| IEC Secretariat3, rue de VarembéCH-1211 Geneva 20Switzerland | Tel.: +41 22 919 02 11 info@iec.ch www.iec.ch |
| IEC publications search - webstore.iec.ch/advsearchform The advanced search enables to find IEC publications by a variety of criteria (reference number, text, technical committee, ...). It also gives information on projects, replaced and withdrawn publications. IEC Just Published - webstore.iec.ch/justpublished Stay up to date on all new IEC publications. Just Published details all new publications released. Available online and once a month by email. IEC Customer Service Centre - webstore.iec.ch/csc If you wish to give us your feedback on this publication or need further assistance, please contact the Customer Service Centre: sales@iec.ch . | IEC Products & Services Portal - products.iec.ch Discover our powerful search engine and read freely all the publications previews. With a subscription you will always have access to up to date content tailored to your needs. Electropedia - www.electropedia.org The world's leading online dictionary on electrotechnology, containing more than 22 300 terminological entries in English and French, with equivalent terms in 19 additional languages. Also known as the International Electrotechnical Vocabulary (IEV) online. |
| IEC 60079-0 |
INTERNATIONAL STANDARD | Edition 7.0 2017-12 | |
| Explosive atmospheres – Part 0: Equipment – General requirements | ||
INTERNATIONAL
ELECTROTECHNCIAL
COMMISSION
| Type | ||||
|---|---|---|---|---|
| Explanation of the significance of the changes | Clause | Minor and editorial changes | Extension | Major technical changes |
| Throughout document, “electrical equipment” replaced by “equipment” where appropriate. | Multiple | X | ||
| Scope
List of “Type of “Protection” and “Product” standards combined into one list. |
1 | X | ||
| Definitions used in multiple sub-parts added.
Definitions harmonized across sub-parts and added to 60079-0 where appropriate.
Battery definitions updated |
3 | X | ||
| Clarification of the way that information on process temperature influences can be expressed. | 5.1.2 | X | ||
| Clarification regarding the determination of service temperatures when dust layers are present | 5.2 | X | ||
| Clarification on the need to provide service temperature information for Ex Components in the Schedule of Limitations | 5.2 | X | ||
| Relocation of EPL Da dust layer requirements from IEC 60079‑18 & IEC 60079‑31 | 5.3.2.3.1 | A1 | ||
| Clarified that for EPL Db, a maximum specified dust layer of greater than 200 mm is not permitted as thicker layers have no additional effect on maximum surface temperature. | b) | X | ||
| Added for EPL Db, a dust layer in a specified orientation, marked as TL | c) | X | ||
| Clarified that for EPL Dc, no dust layer tests are required. | 5.3.2.3.3 | X | ||
| Clarified that the “temperature” is the temperature of the air surrounding the component | 5.3.3 | X | ||
| Subdivided section dealing with higher permitted surface temperatures for “smooth” surfaces. Corrected area from 1 000 mm2 to 10 000 mm2. | 5.3.4 | X | ||
| Clarified that the “Ex” requirements of IEC 60079 supplement those of the relevant industrial standards. | 6.1 | X | ||
| Added requirement that where an adhesive is used to secure a gasket, it shall be used within its COT and shall comply with the requirements for cements. | 6.5 | C1 | ||
| Requirements relocated to IEC 60079‑28 | former 6.6.2 | A2 | ||
| Ultrasonic requirements updated based on latest research work | 6.6.3 | X | ||
| Added reference to IEC 60079‑28 | 6.6.4 | A2 | ||
| Material identification parameters have been revised to reflect reasonably obtainable information | 7.1.2.2 | X | ||
| “RTI-mechanical” has been clarified to include “RTI-mechanical strength” and “RTI-mechanical impact” | 7.1.2.2 | X | ||
| Material identification parameters have been revised to reflect reasonably obtainable information | 7.1.2.3 | X | ||
| Relocated information on “cements” from Clause 12. | 7.1.2.4 | X | ||
| “RTI-mechanical” has been clarified to include “RTI-mechanical strength” and “RTI-mechanical impact”. Requirements for cements aligned with the requirements for elastomers. | 7.2.2 | X | ||
| Relocation of 10 K margin for EPL Gc or Dc from IEC 60079‑15, IEC 60079‑18 & IEC 60079‑31 | 7.2.2 | A3 | ||
| Added clarification with respect to gaskets and seals where only the outer edge is potentially exposed to light. | 7.3 | X | ||
| Clarification added that one or more of the described techniques may be used | 7.4.2 | X | ||
| Added additional relaxation for the case where a surface is in contact with an earthed surface on only two of four sides. | 7.4.2 b) | X | ||
| Added reference to IEC 60243‑1 and IEC 60243‑2 for test method to require a 4 kV DC test.. | 7.4.2.c) | C2 | ||
| Additional guidance added with respect to the possible Specific Conditions of Use | 7.4.2 e) | X | ||
| New option added for portable, mains-powered equipment with earth-connected guard | 7.4.2 f) | X | ||
| Added option for determination of maximum transferred charge. | 7.4.2 g) Table 10 | X | ||
| Added missing limits (same as 7.4.2) | 7.4.3 a) | X | ||
| Clarified that it is a dc test that is conducted | 7.4.3 b) | X | ||
| Clarified that this requirement is not applied to personal or portable equipment | 7.5 | X | ||
| Clarified Group I limits | 8.2 | X | ||
| Clarified Group II, EPL Ga limits | 8.3 | X | ||
| Added limitation for external surfaces of >65% copper | 8.5 | C3 | ||
| Added clarification as to what is considered a tool | 9.1 | X | ||
| Clarified that the tolerance class of the set screw is not critical, only that it not protrude from the threaded hole after tightening. | 9.4 | X | ||
| Information on cements transferred to Clause 7 | 12 | X | ||
| Required that Ex Component Certificates require a Schedule of Limitations in all cases | 13.5 | X | ||
| Revised to clarified that all connection facilities may not be a “Compartment”. | 14 | X | ||
| Sub-clause split to separate the requirements for protective earthing and equipotential bonding into separate sections | 15.3 15.4 | X | ||
| Section split to separate secureness of electrical connections from the internal earth continuity plate. | 15.6 15.7 | X | ||
| Non-threaded Group I cable glands are no longer required to be Ex Components. | 16.3 | X | ||
| Non-threaded Group I blanking elements are no longer required to be Ex Components. | 16.4 | X | ||
| Scope of Clause 17 clarified to define applicability | 17 | X | ||
| Additional guidance notes added to address bearings | 17.3 | X | ||
| Clarified applicability to disconnectors, interlocks, and maintenance switches. | 18.2 | X | ||
| Fuse requirements deleted as they are addressed in the individual sub-parts | 19 | X | ||
| Added requirements for EPL Gc and Dc | 20.1 | C4 | ||
| The test circuit requirements for a flameproof connection have been removed as they are more completely specified in IEC 60079‑1. | 20.2 | X | ||
| The impact test requirements for luminaires are relocated to Table 15 | 21.1 Table 15 | X | ||
| Clarified interlock switch operation for flameproof luminaires | 21.2 | X | ||
| Clarified that some Types of Protection permit connection of cells in parallel | 23.2 | X | ||
| New cell types and data added based on latest available data | Table 13 | X | ||
| New cell types and data added based on latest available data | Table 14 | C5 | ||
| Clarification of what documentation is to be prepared regarding the explosion safety aspects of the equipment | 24 | X | ||
| Clarification that the type tests are to take into consideration the installation instructions | 26.2 | X | ||
| Clarification that the “glass” requirements also apply to “ceramic” parts | 26.4.1.1 | X | ||
| Added a permission to interchange the order of tests at the “lower test temperature” and the “upper test temperature”. | 26.4.1.2.2 26.4.1.2.3 | X | ||
| Clarified the construction of the impact test fixture | 26.4.2 | X | ||
| Clarified the impact tests for glass parts | 26.4.2 | X | ||
| Added clarification to deal with the new IPX9 ratings | 26.4.5.1 | X | ||
| Clarified the test voltage for maximum surface temperature | 26.5.1.3 | X | ||
| Relocation of EPL Da dust layer requirements from IEC 60079‑18 & IEC 60079‑31 | 26.5.1.3 | A1 | ||
| Relocation of EPL Db specified dust layer requirements from IEC 60079‑31 | 26.5.1.3 | A4 | ||
| Added for EPL Db, a dust layer in a specified orientation, marked as TL | 26.5.1.3 | B1 | ||
| Clarified that for EPL Dc, the testing is conducted without a dust layer. | 26.5.1.3 | X | ||
| Relocation of thermal endurance to heat 10K relaxation for Gc equipment from IEC 60079‑15, IEC 60079‑18, & IEC 60079‑31 | Table 17 | X | ||
| Clarification of a consistent way to address elastomeric materials exposed to ultraviolet light | 26.10 | X | ||
| Replacement of “oil No. 2” with the revised designation of “oil IRM 902”. | 26.11 | X | ||
| Option added for testing at lower voltages when low resistance materials are encountered | 26.13 | X | ||
| Transferred charge test added based on IEC TS 60079‑32‑2 | 26.17 | X | ||
| The reference to a specific instruction document instead of an “X” condition relocated to e) instead of a note giving a permission | 29.3 e) | X | ||
| Updated to reflect the additional levels of protection already shown in the sub-parts: “da”, “dc”, “eb”, “ec”, “oc”, “op is”, “op pr”, “op sh”, “pxb”, “pyb”, “pzc”, “qb”, “sa”, “sb”, and “sc”. | 29.4 b) | X | ||
| Text added to address marking of “Ex associated equipment” | 29.4 | X | ||
| Updated to reflect the additional levels of protection already shown in the sub-parts: “ic”, “op is”, “op pr”, “op sh”, “pxb”, “pyb”, “pzc”, “sa”, “sb”, and “sc”. | 29.5 b) | X | ||
| Clarified marking of EPL Da, EPL Db with no dust layer, EPL Db with a specified dust layer, and EPL Dc. | 29.5 d) | X | ||
| Introduced marking for EPL Db with a dust layer in a specified orientation | 29.5 d) | X | ||
| Text added to address marking of “Ex associated equipment” | 29.5 | X | ||
| Text added to address marking of equipment intended to be installed in a boundary wall. | 29.9 | X | ||
| The marking of Ex Component enclosure was aligned with the marking requirements of IEC 60079‑1 and IEC 60079‑7 | 29.10 | X | ||
| The alternate marking of EPL has been deleted. | former 29.13 | C6 | ||
| Marking for electric machines operated with a converter clarified | 29.15 | X | ||
| Instruction material guidance clarified | 30.1 | X | ||
| Additional instruction material for electric machines added | 30.3 | C7 | ||
| Additional instruction material for cable glands added | 30.5 A.5 | C8 | ||
| Allow ISO 10807 hose assemblies to be used with cable glands. | A.1 | X | ||
| Clarify testing with stainless steel mandrels | A.3 | X | ||
| Reduction of the time / slippage permitted | A.3.1.1 | X | ||
| Clarify impact testing of cable glands | A.3.3 Figure A.3 | X | ||
| Clarified the order of tests | A.3.4 | X | ||
| Clarified remarks | Annex B | X | ||
| Aligned Figure with text | Figure C.1 | X | ||
| Clarified operation of electric machines from converters | Annex D (informative) | X | ||
| Clarified temperature testing of electric machines | Annex E (informative) | X | ||
| Flowchart for Cable Gland testing | Annex G (informative) | X | ||
| Guidance of electric machine shaft voltages | Annex H (informative) | X | ||
| Minor and editorial changes | clarification |
| decrease of technical requirements | |
| minor technical change | |
| editorial corrections |
| Extension | addition of technical options |
| Major technical changes | addition of technical requirements |
| increase of technical requirements |
| A1 | The dust layer requirements for EPL Da are unchanged from what previously existed in IEC 60079‑18, Ed 4 and IEC 60079‑31, Ed 2, but have been relocated to IEC 60079‑0 to allow consistent application in all Types of Protection. |
| A2 | IEC 60079‑28 now includes all requirements for optical radiation for all EPLs. |
| A3 | The COT requirements for EPL Gc or Dc are unchanged from what previously existed in IEC 60079‑15, Ed 4, IEC 60079‑18, Ed 4, and IEC 60079‑31, Ed 2, but have been relocated to IEC 60079‑0 to allow consistent application in all Types of Protection. |
| A4 | The dust layer requirements for EPL Db with a specified dust layer depth are unchanged from what previously existed in IEC 60079‑31, Ed 2, but have been relocated to IEC 60079‑0 to allow consistent application in all Types of Protection. |
| B1 | Dust layer requirements for EPL Db with a dust layer in a specified orientation have been added. |
| C1 | It is recognized that the new requirements were, in many cases, already applied. The change is to ensure that they are uniformly and consistently applied. |
| C2 | Require that the test be conducted at 4 kV DC. |
| C3 | The limitation applies to external surfaces of other than cable glands, blanking elements, thread adapters and bushings. |
| C4 | The added requirements for tool securing and marking are consistent with the approach in IEC 60079‑15 |
| C5 | Voltage values were changed following additional research due to the complicated assessment and sometimes unspecified construction of Li/Ion-cells. It was found that some voltage values previously stated were too low. |
| C6 | The now required EPL marking may be other than that permitted by the Level of Protection to account for limiting restrictions of material or plastic material surface area. |
| C7 | Additional instruction material for electric machines required to facilitate selection, installation, and maintenance. |
| C8 | Additional instruction material for cable glands required to facilitate selection and installation. |
| FDIS | Report on voting |
| 31/1345/FDIS | 31/1356/RVD |
Figure 1 — Typical battery examples | |||||||
|
Figure 2 — Typical battery compartment | |||||||||
|
Figure 3 — Typical replaceable battery pack | |||||||
|