GSO IEC 60364-5-54:2016
GSO - Cover page
Gulf Foreword
IEC - Cover page
FOREWORD
INTRODUCTION
541 General
 541.1 Scope
 541.2 Normative references
 541.3 Terms and definitions
542 Earthing arrangements
 542.1 General requirements
 542.2 Earth electrodes
 542.3 Earthing conductors
 542.4 Main earthing terminal
543 Protective conductors
 543.1 Minimum cross-sectional areas
 543.2 Types of protective conductors
 543.3 Electrical continuity of protective conductors
 543.4 PEN, PEL or PEM conductors
 543.5 Combined protective and functional earthing conductors
 543.6 Currents in protective earthing conductors
 543.7 Reinforced protective earthing conductors for protective earthing conductor currents exceeding 10 mA
 543.8 Arrangement of protective conductors
544 Protective bonding conductors
 544.1 Protective bonding conductors for connection to the main earthing terminal
 544.2 Protective bonding conductors for supplementary bonding
Annex A Method for deriving the factor k in 543.1.2 (see also IEC 60724 and IEC 60949)
Annex B Example of earthing arrangements and protective conductors
Annex C Erection of concrete-embedded foundation earth electrodes
Annex D Erection of soil-embedded earth electrodes
Annex E List of notes concerning certain countries
Bibliography
30mm
20mm
15mm
15mm
10mm
17mm
Gulf StandardGSO IEC 60364-5-54:2016
Gulf StandardGSO IEC 60364-5-54:2016
GSO IEC 60364-5-54:2016Gulf Standard
GSO IEC 60364-5-54:2016
IEC 60364-5-54:2011
مواصفة قياسية خليجية
التركيبات الكهربائية ذات الجهد المنخفض -الجزء 5-54: اختيار وتثبيت المعدات الكهربائية-ترتيبات التأريض، موصلات الحماية، وموصلات الحماية المساعدة
Gulf Standard
Low voltage electrical installations - Part 5-54: Selection and erection of electrical equipment - Earthing arrangements, protective conductors and protective bonding conductors
ICS:
29.020 ; 91.140.50

graphic
هذه الوثيقة محمية بالقانون
COPYRIGHT PROTECTED DOCUMENT
جميع الحقوق محفوظة لهيئة لتقييس لدول مجلس التعاون لدول الخليج العربية.
ما لم ينص على خلاف ذلك، لا يجوز إعادة إنتاج أي جزء من هذا المنشور أو استخدامه بأي شكل آخر أو بأي وسيلة، إلكترونية أو ميكانيكية، بما في ذلك التصوير، أو النشر على الإنترنت أو الإنترانت، دون إذن كتابي مسبق من هيئة التقييس لدول مجلس التعاون لدول الخليج العربية على العنوان أدناه أو الدول الأعضاء في الهيئة داخل بلدانهم.
All rights reserved to GCC Standardization Organization (GSO). Unless otherwise specified, no part of this publication may be reproduced or utilized otherwise in any form or by any means, electronic or mechanical, including photocopying, or posting on the internet or an intranet, without prior written permission. Permission can be requested from either GSO at the address below or GSO's member body in the country of the requester.
Outreach Dept, Knowledge Management Section
GCC Standardization Organization (GSO)
P.O.Box: 85245 Riyadh 12511
Kingdom of Saudi Arabia
إدارة التواصل، قسم إدارة المعرفة
هيئة التقييس لدول مجلس التعاون لدول الخليج العربية (GSO)
ص. ب: 85245 الرياض 12511
المملكة العربية السعودية
Tel: +966115208000 :هاتف
Fax: +966115208010 :فاكس
E-Mail: csc@gso.org.sa :بريد إلكتروني
Website: www.gso.org.sa :موقع ويب
30mm
20mm
15mm
15mm
10mm
17mm

Gulf StandardGSO IEC 60364-5-54:2016
Gulf StandardGSO IEC 60364-5-54:2016
GSO IEC 60364-5-54:2016Gulf Standard

Gulf Foreword

GCC Standardization Organization (GSO) is a regional organization which consists of the national standardization bodies of GCC member states. One of GSO main functions is to issue gulf standards and technical regulations through specialized technical committees.
GSO Technical Council in its meeting number (39) held on 24/12/1437 H, which corresponds to 27/09/2016, has approved the update of Gulf Standard GSO IEC 60364-5-54:2016 titled "Low voltage electrical installations - Part 5-54: Selection and erection of electrical equipment - Earthing arrangements, protective conductors and protective bonding conductors " in English language which was studied and adopted by endorsement from International Electrotechnical Commission Standard IEC 60364-5-54:2011 through the technical program of GSO Technical Committee for Electrical and Electronic Products (TC03) in KUWAIT schedule . This document will cancel and replace the Gulf Standard GSO IEC 60364-5-54:2008.
تقديم خليجي
هيئة التقييس لدول مجلس التعاون لدول الخليج العربية هيئة إقليمية تضم في عضويتها أجهزة التقييس الوطنية في الدول الأعضاء ، ومن مهام الهيئة إعداد المواصفات القياسية واللوائح الفنية الخليجية بواسطة لجان فنية متخصصة.
قرر المجلس الفني لهيئة التقييس لدول مجلس التعاون لدول الخليج العربية في الاجتماع الـ (39) بتاريخ 1437/12/24 هـ ،الموافق 2016/09/27م اعتماد تحديث المواصفة القياسية الخليجية رقم GSO IEC 60364-5-54:2016 وعنوانها "التركيبات الكهربائية ذات الجهد المنخفض -الجزء 5-54: اختيار وتثبيت المعدات الكهربائية-ترتيبات التأريض، موصلات الحماية، وموصلات الحماية المساعدة" باللغة الانجليزية التي تم دراستها وتبنيها بالمصادقة عن اللجنة الدولية الكهروتقنية رقم IEC 60364-5-54:2011 ضمن برنامج عمل اللجنة الفنية الخليجية للمواصفات الكهربائية والإلكترونية (TC03) المدرجة في خطة دولة الكويت . على أن تلغي وتحل محل المواصفة القياسية رقم GSO IEC 60364-5-54:2008 .
30mm
20mm
15mm
15mm
10mm
17mm
Gulf StandardGSO IEC 60364-5-54:2016
Gulf StandardGSO IEC 60364-5-54:2016
Gulf StandardGSO IEC 60364-5-54:2016
GSO IEC 60364-5-54:2016Gulf Standard
IEC 60364-5-54

INTERNATIONAL

STANDARD

Edition 3.0  2011-03
Low-voltage electrical installations –
Part 5-54: Selection and erection of electrical equipment – Earthing arrangements and protective conductors
IEC 60364-5-54:2011 ED3
30mm
20mm
15mm
15mm
10mm
17mm
Gulf StandardGSO IEC 60364-5-54:2016
Gulf StandardGSO IEC 60364-5-54:2016
Gulf StandardGSO IEC 60364-5-54:2016
GSO IEC 60364-5-54:2016Gulf Standard
THIS PUBLICATION IS COPYRIGHT PROTECTEDCopyright © 2011 IEC, Geneva, Switzerland
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form or by any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from either IEC or IEC's member National Committee in the country of the requester. If you have any questions about IEC copyright or have an enquiry about obtaining additional rights to this publication, please contact the address below or your local IEC member National Committee for further information.
IEC Secretariat3, rue de VarembéCH-1211 Geneva 20Switzerland Tel.: +41 22 919 02 11 info@iec.ch www.iec.ch
About the IEC The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes International Standards for all electrical, electronic and related technologies. About IEC publications The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the latest edition, a corrigendum or an amendment might have been published.
IEC publications search - webstore.iec.ch/advsearchform The advanced search enables to find IEC publications by a variety of criteria (reference number, text, technical committee, ...). It also gives information on projects, replaced and withdrawn publications. IEC Just Published - webstore.iec.ch/justpublished Stay up to date on all new IEC publications. Just Published details all new publications released. Available online and once a month by email. IEC Customer Service Centre - webstore.iec.ch/csc If you wish to give us your feedback on this publication or need further assistance, please contact the Customer Service Centre: sales@iec.ch .   IEC Products & Services Portal - products.iec.ch Discover our powerful search engine and read freely all the publications previews. With a subscription you will always have access to up to date content tailored to your needs. Electropedia - www.electropedia.org The world's leading online dictionary on electrotechnology, containing more than 22 300 terminological entries in English and French, with equivalent terms in 19 additional languages. Also known as the International Electrotechnical Vocabulary (IEV) online.
30mm
20mm
15mm
15mm
10mm
17mm
Gulf StandardGSO IEC 60364-5-54:2016
Gulf StandardGSO IEC 60364-5-54:2016
Gulf StandardGSO IEC 60364-5-54:2016
GSO IEC 60364-5-54:2016Gulf Standard
IEC 60364-5-54

INTERNATIONAL

STANDARD

Edition 3.0  2011-03
Low-voltage electrical installations –
Part 5-54: Selection and erection of electrical equipment – Earthing arrangements and protective conductors

INTERNATIONAL

ELECTROTECHNCIAL

COMMISSION


ICS 29.020, 91.140.50ISBN 9782889124008Warning! Make sure that you obtained this publication from an authorized distributor.© Registered trademark of the International Electrotechnical Commission
30mm
20mm
15mm
15mm
10mm
17mm

Gulf StandardGSO IEC 60364-5-54:2016
Gulf StandardGSO IEC 60364-5-54:2016
Gulf StandardGSO IEC 60364-5-54:2016
GSO IEC 60364-5-54:2016Gulf Standard
CONTENTS
INTERNATIONAL ELECTROTECHNICAL COMMISSION
International StandardIEC 60364-5-54:2011 ED3
Low-voltage electrical installations - Part 5-54: Selection and erection of electrical equipment - Earthing arrangements and protective conductors

FOREWORD

1)
The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising all national electrotechnical committees (IEC National Committees). The object of IEC is to promote international co-operation on all questions concerning standardization in the electrical and electronic fields. To this end and in addition to other activities, IEC publishes International Standards, Technical Specifications, Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested in the subject dealt with may participate in this preparatory work. International, governmental and non-governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely with the International Organization for Standardization (ISO) in accordance with conditions determined by agreement between the two organizations.
2)
The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international consensus of opinion on the relevant subjects since each technical committee has representation from all interested IEC National Committees.
3)
IEC Publications have the form of recommendations for international use and are accepted by IEC National Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any misinterpretation by any end user.
4)
In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications transparently to the maximum extent possible in their national and regional publications. Any divergence between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in the latter.
5)
IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any services carried out by independent certification bodies.
6)
All users should ensure that they have the latest edition of this publication.
7)
No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and members of its technical committees and IEC National Committees for any personal injury, property damage or other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC Publications.
8)
Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is indispensable for the correct application of this publication.
9)
Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 60364‑5‑54 has been prepared by IEC technical committee 64: Electrical installations and protection against electric shock.
This third edition cancels and replaces the second edition, published in 2002, and constitutes a technical revision.
The main changes with respect to the previous edition are listed below:
–
clarification of the definition of protective conductor;
–
improved specification of mechanical characteristics of the earth electrode;
–
introduction of earth electrode for protection against electric shock and lighting protection;
–
annexes describing concrete-embedded foundation earth electrodes and soil-embedded earth electrode.
The text of this standard is based on the following documents:
FDIS Report on voting
64/1755/FDIS 64/1766/RVD
Full information on the voting for the approval of this standard can be found in the report on voting indicated in the above table.
It has the status of a basic safety publication in accordance with IEC Guide 104.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.
The reader's attention is drawn to the fact that Annex E lists all of the "in-some-country" clauses on differing practices of a less permanent nature relating to the subject of this standard.
A list of all parts in the IEC 60364 series, under the general title: Low-voltage electrical installations, can be found on the IEC website.
The committee has decided that the contents of this publication will remain unchanged until the stability date indicated on the IEC web site under "http://webstore.iec.ch" in the data related to the specific publication. At this date, the publication will be
•
reconfirmed,
•
withdrawn,
•
replaced by a revised edition, or
•
amended.

INTRODUCTION

Clause numbering is sequential, preceded by the number of this Part. Numbering of figures and tables takes the number of this part followed by a sequential number, i.e. Table 54.1, 54.2, etc. Numbering of figures and tables in annexes takes the letter of the annex, followed by the number of the part, followed by a sequential number, e.g. A.54.1, A.54.2, etc.
30mm
20mm
15mm
15mm
10mm
17mm

Gulf StandardGSO IEC 60364-5-54:2016
Gulf StandardGSO IEC 60364-5-54:2016
Gulf StandardGSO IEC 60364-5-54:2016
GSO IEC 60364-5-54:2016Gulf Standard
International StandardIEC 60364-5-54:2011 ED3
Low-voltage electrical installations - Part 5-54: Selection and erection of electrical equipment - Earthing arrangements and protective conductors

541General

541.1Scope

This part of IEC 60364 addresses the earthing arrangements and protective conductors including protective bonding conductors in order to satisfy the safety of the electrical installation.

541.2Normative references

The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.
IEC 60364‑4‑41:2005, Low-voltage electrical installations – Part 4-41: Protection for safety – Protection against electric shock
IEC 60364‑4‑44:2007, Low-voltage electrical installations – Part 4-44: Protection for safety – Protection against voltage disturbances and electromagnetic disturbances
IEC 60364‑5‑51:2005, Electrical installations of buildings – Part 5-51: Selection and erection of electrical equipment – Common rules
IEC 60439‑2, Low-voltage switchgear and controlgear assemblies – Part 2: Particular requirements for busbar trunking systems (busways)
IEC 61439‑1, Low-voltage switchgear and controlgear assemblies – Part 1: General rules
IEC 61439‑2, Low-voltage switchgear and controlgear assemblies – Part 2: Power switchgear and controlgear assemblies
IEC 60724, Short-circuit temperature limits of electric cables with rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV)
IEC 60909‑0, Short-circuit currents in three-phase a.c. systems – Part 0: Calculation of currents
IEC 60949, Calculation of thermally permissible short-circuit currents, taking into account non-adiabatic heating effects
IEC 61140:2001, Protection against electric shock – Common aspects for installation and equipment
IEC 61534‑1, Powertrack systems – Part 1: General requirements
IEC 62305 (all parts), Protection against lightning
IEC 62305‑3:2006, Protection against lightning – Part 3: Physical damage to structures and life hazard

541.3Terms and definitions

For the purposes of this document, the terms and definitions of IEC 61140, together with the following definitions, apply.
Definitions used for earthing arrangements, protective conductors and protective bonding conductors are illustrated in Annex B and listed below:
541.3.1
exposed-conductive-part
conductive part of equipment which can be touched and which is not normally live, but which can become live when basic insulation fails
[SOURCE: IEC 60050‑826:2004, 826‑12‑10]
541.3.2
extraneous-conductive-part
conductive part not forming part of the electrical installation and liable to introduce an electric potential, generally the electric potential of a local earth
[SOURCE: IEC 60050‑825:2004, IEV 826‑12‑11]
541.3.3
earth electrode
conductive part, which may be embedded in the soil or in a specific conductive medium, e.g. concrete, in electrical contact with Earth
[SOURCE: IEC 60050‑826:2004, 826‑13‑05
modified
]
541.3.4
concrete-embedded foundation earth electrode
earth electrode embedded in concrete of a building foundation, generally in the form of a closed loop
[SOURCE: IEC 60050‑826:2004, 826‑13‑08
modified
]
541.3.5
soil-embedded foundation earth electrode
earth electrode buried in the soil under a building foundation, generally in the form of a closed loop
[SOURCE: IEC 60050‑826:2004, 826‑13‑08
modified
]
541.3.6
protective conductor
conductor provided for purposes of safety, for example protection against electric shock
[SOURCE: IEC 60050‑826:2004, 826‑13‑22]
Note 1 to entry: Examples of a protective conductor include a protective bonding conductor, a protective earthing conductor and an earthing conductor when used for protection against electric shock.
541.3.7
protective bonding conductor
protective conductor provided for protective-equipotential-bonding
[SOURCE: IEC 60050‑826:2004, 826‑13‑24]
541.3.8
earthing conductor
conductor which provides a conductive path, or part of the conductive path, between a given point in a system or in an installation or in equipment and an earth-electrode network
[SOURCE: IEC 60050‑826:2004, 826‑13‑12]
Note 1 to entry: For the purposes of this part of IEC 60364, an earthing conductor is the conductor which connects the earth electrode to a point in the equipotential bonding system, usually the main earthing terminal.
541.3.9
main earthing terminal
main earthing busbar
terminal or busbar which is part of the earthing arrangement of an installation and enabling the electrical connection of a number of conductors for earthing purposes
[SOURCE: IEC 60050‑826:2004, 826‑13‑15]
541.3.10
protective earthing conductor
protective conductor provided for protective earthing
[SOURCE: IEC 60050‑826:2004, 826‑13‑23]
541.3.11
functional earthing
earthing a point or points in a system or in an installation or in equipment, for purposes other than electrical safety
[SOURCE: IEC 60050‑826:2004, IEV 826‑13‑10]
541.3.12
earthing arrangement
all the electrical connections and devices involved in the earthing of a system, installation or an equipment
[SOURCE: IEC 60050‑195:2004, 195‑02‑20]

542Earthing arrangements

542.1General requirements

542.1.1The earthing arrangements may be used jointly or separately for protective and functional purposes according to the requirements of the electrical installation. The requirements for protective purposes shall always take precedence.
542.1.2Where provided, earth electrodes within an installation shall be connected to the main earthing terminal using an earthing conductor.
NOTEAn installation does not need to have its own earth electrode.
542.1.3Where the supply to an installation is at high voltage, requirements concerning the earthing arrangements of the high voltage supply and of the low-voltage installation shall also comply with Clause 442 of IEC 60364‑4‑44:2007.
542.1.4The requirements for earthing arrangements are intended to provide a connection to earth which:
–
is reliable and suitable for the protective requirements of the installation;
–
can carry earth fault currents and protective conductor currents to earth without danger from thermal, thermo-mechanical and electromechanical stresses and from electric shock arising from these currents;
–
if relevant, is also suitable for functional requirements;
–
is suitable for the foreseeable external influences (see IEC 60364‑5‑51), e.g. mechanical stresses and corrosion.
542.1.5Consideration shall be given to the earthing arrangements where currents with high frequencies are expected to flow (see Clause 444 of IEC 60364‑4‑44:2007).
542.1.6Protection against electric shock, as stated in IEC 60364‑4‑41, shall not be adversely affected by any foreseeable change of the earth electrode resistance (e.g. due to corrosion, drying or freezing).

542.2Earth electrodes

542.2.1The type, materials and dimensions of earth electrodes shall be selected to withstand corrosion and to have adequate mechanical strength for the intended lifetime.
NOTE 1For corrosion, the following parameters may be considered: the soil pH at the site, soil resistivity, soil moisture, stray and leakage a.c. and d.c. current, chemical contamination, and proximity of dissimilar materials.
For materials commonly used for earth electrodes, the minimum sizes, from the point of view of corrosion and mechanical strength, when embedded in the soil or in concrete, shall be as specified in Table 54.1.
NOTE 2The minimum thickness of protective coating is greater for vertical earth electrodes than for horizontal earth electrodes because of their greater exposure to mechanical stresses while being embedded.
If a lightning protection system is required, 5.4 of IEC 62305‑3:2006 applies.
Table 54.1 — Minimum size of commonly used earth electrodes, embedded in soil or concrete used to prevent corrosion and provide mechanical strength
Material and surface Shape Diameter Cross-sectional area Thickness Weight of coating Thickness of coating/ sheathing
mm mm2 mm g/m2 μm
Steel embedded in concrete (bare, hot galvanized or stainless) Round wire 10
Solid tape or strip 75 3
Steel hot-dip galvanizedc Stripb or shaped strip/plate – Solid plate – Lattice plate 90 3 500 63
Round rod installed vertically 16 350 45
Round wire installed horizontally 10 350 45
Pipe 25 2 350 45
Stranded (embedded in concrete) 70
Cross profile installed vertically (290) 3
Steel copper-sheathed Round rod installed vertically (15) 2 000
Steel with electro-deposited copper coating Round rod installed vertically 14 250e
Round wire installed horizontally (8) 70
Strip installed horizontally 90 3 70
Stainless steela Stripb or shaped strip/plate 90 3
Round rod installed vertically 16
Round wire installed horizontally 10
Pipe 25 2
Copper Strip 50 2
Round wire installed horizontally (25)d 50
Solid round rod installed vertically (12) 15
Stranded wire 1,7 for individual strands of wire (25)d 50
Pipe 20 2
Solid plate (1,5) 2
Lattice plate 2
NOTEValues in brackets are applicable for protection against electric shock only, while values not in brackets are applicable for lightning protection and for protection against electric shock.
aChromium ≥16 %, Nickel ≥5 %, Molybdenum ≥2 %, Carbon ≤0,08 %.
bAs rolled strip or slit strip with rounded edges.
cThe coating shall be smooth, continuous and free from flux stains.
dWhere experience shows that the risk of corrosion and mechanical damage is extremely low, 16 mm2 can be used.
eThis thickness is provided to withstand mechanical damage of copper coating during the installation process. It may be reduced to not less than 100 μm where special precautions to avoid mechanical damage of copper during the installation process (e.g. drilled holes or special protective tips) are taken according to the manufacturer’s instructions.
542.2.2The efficacy of any earth electrode depends on its configuration and upon local soil conditions. One or more earth electrodes suitable for the soil conditions and the value of resistance to earth required shall be selected.
Annex D gives methods of estimation of earth electrode resistance.
542.2.3The following are examples of earth electrodes which may be used:
–
concrete-embedded foundation earth electrode;
NOTEFor more information see Annex C.
–
soil-embedded foundation earth electrode;
–
metallic electrode embedded directly in soil vertically or horizontally (e.g. rods, wires, tapes, pipes or plates);
–
metal sheath and other metal coverings of cables according to local conditions or requirements;
–
other suitable underground metalwork (e.g. pipes) according to local conditions or requirements;
–
welded metal reinforcement of concrete (except pre-stressed concrete) embedded in the earth.
542.2.4When selecting the type and embedded depth of an earth electrode, consideration shall be given to possible mechanical damage and to local conditions to minimize the effect of soil drying and freezing.
542.2.5Consideration shall be given to electrolytic corrosion when using different materials in an earthing arrangement. For external conductors (e.g. earthing conductor) connected to a concrete-embedded foundation earth electrode, the connection made from hot-dip galvanized steel shall not be embedded in the soil.
542.2.6The earthing arrangement shall not rely on a metallic pipe for flammable liquids or gases as the earth electrode and their buried length shall not be considered when dimensioning the earth electrode.
NOTEThis requirement does not preclude the protective equipotential bonding via the main earthing terminal (541.3.9) of such pipes for compliance with IEC 60364‑4‑41.
Where cathodic protection is applied and the exposed-conductive-part of an item of electrical equipment supplied by a TT system is directly connected to the pipe, a metallic pipe for flammable liquids or gases may act as the sole earth electrode for this specific equipment.
542.2.7Earth electrodes shall not be directly immersed in water of a stream, river, pond, lake or the like (see also 542.1.6).
542.2.8Where an earth electrode consists of parts that must be connected together, the connection shall be by exothermic welding, pressure connectors, clamps or other suitable mechanical connectors.
NOTEConnections made by a wrapped iron wire only are not suitable for protection purposes.

542.3Earthing conductors

542.3.1Earthing conductors shall comply with 543.1.1 or 543.1.2. Their cross-sectional area shall be not less than 6 mm2 for copper or 50 mm2 for steel. Where a bare earthing conductor is buried in the soil, its dimensions and characteristics shall also be in accordance with Table 54.1.
Where no noticeable fault current is expected to flow through the earth electrode (e.g. in TN systems or IT systems), the earthing conductor may be dimensioned according to 544.1.
Aluminium conductors shall not be used as earthing conductors.
NOTEWhere a lightning protection system is connected to the earth electrode, the cross-sectional area of the earthing conductor should be at least 16 mm2 for copper (Cu) or 50 mm2 for iron (Fe) (see the IEC 62305 series).
542.3.2The connection of an earthing conductor to an earth electrode shall be soundly made and electrically satisfactory. The connection shall be by exothermic welding, pressure connectors, clamps or other suitable mechanical connectors. Mechanical connectors shall be installed in accordance with the manufacturer’s instructions. Where a clamp is used, it shall not damage the electrode or the earthing conductor.
Connection devices or fittings that depend solely on solder shall not be used independently, as they do not reliably provide adequate mechanical strength.
NOTEWhere vertical electrodes are installed, means may be provided to allow the inspection of the connection and the replacement of the vertical rod.

542.4Main earthing terminal

542.4.1In every installation where protective equipotential bonding is used, a main earthing terminal shall be provided and the following shall be connected to it:
–
protective bonding conductors;
–
earthing conductors;
–
protective conductors;
–
functional earthing conductors, if relevant.
NOTE 1It is not intended to connect every individual protective conductor directly to the main earthing terminal where they are connected to this terminal by other protective conductors.
NOTE 2The main earthing terminal of the building can generally be used for functional earthing purposes. For information technology purposes, it is then regarded as the connection point to the earth.
Where more than one earthing terminal is provided, they shall be interconnected.
542.4.2Each conductor connected to the main earthing terminal shall be able to be disconnected individually. This connection shall be reliable and such that it can only be disconnected by means of a tool.
NOTEDisconnection means may conveniently be combined with the main earthing terminal, to permit measurement of the resistance of the earth electrode.
30mm
20mm
15mm
15mm
10mm
17mm

Gulf StandardGSO IEC 60364-5-54:2016
Gulf StandardGSO IEC 60364-5-54:2016
Gulf StandardGSO IEC 60364-5-54:2016
GSO IEC 60364-5-54:2016Gulf Standard
Bibliography
IEC 60050‑195:1998, International Electrotechnical Vocabulary – Part 195: Earthing and protection against electric shock
IEC 60050‑826:2004, International Electrotechnical Vocabulary – Part 826: Electrical installations
IEC 60079‑0, Explosive atmospheres– Part 0: Equipment – General requirements
IEC 60079‑14, Explosive atmospheres – Part 14: Electrical installations design, selection and erection
IEC 60364‑4‑43, Low-voltage electrical installations – Part 4-43: Protection for safety – Protection against overcurrent
IEC 60364‑5‑52, Low-voltage electrical installations – Part 5-52: Selection and erection of electrical equipment – Wiring systems
IEC 60364‑6, Low-voltage electrical installations – Part 6: Verification
IEC 60364‑7‑701:2006, Low-voltage electrical installations – Part 7-701: Requirements for special installations or locations – Locations containing a bath or shower
IEC 60702‑1, Mineral insulated cables and their terminations with a rated voltage not exceeding 750 V – Part 1: Cables
IEC 61643‑12, Low-voltage surge protective devices – Part 12: Surge protective devices connected to low-voltage power distribution systems – Selection and application principles
National Standard DIN 18014:1994, Fundamenterder ("Foundation earth electrode" in English)
30mm
20mm
15mm
15mm
10mm
17mm
INTERNATIONALELECTROTECHNICALCOMMISSION3, rue de VarembéPO Box 131CH-1211 Geneva 20SwitzerlandTel: +41 22 919 02 11info@iec.chwww.iec.ch