Low-voltage electrical installations - Part 5-54: Selection and erection of electrical equipment - Earthing arrangements and protective conductors
541General
541.1Scope
This part of IEC 60364 addresses the earthing arrangements and protective conductors including protective bonding conductors in order to satisfy the safety of the electrical installation.
541.2Normative references
The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.
IEC 60364‑4‑41:2005, Low-voltage electrical installations – Part 4-41: Protection for safety – Protection against electric shock
IEC 60364‑4‑44:2007, Low-voltage electrical installations – Part 4-44: Protection for safety – Protection against voltage disturbances and electromagnetic disturbances
IEC 60364‑5‑51:2005, Electrical installations of buildings – Part 5-51: Selection and erection of electrical equipment – Common rules
IEC 60439‑2, Low-voltage switchgear and controlgear assemblies – Part 2: Particular requirements for busbar trunking systems (busways)
IEC 61439‑1, Low-voltage switchgear and controlgear assemblies – Part 1: General rules
IEC 61439‑2, Low-voltage switchgear and controlgear assemblies – Part 2: Power switchgear and controlgear assemblies
IEC 60724, Short-circuit temperature limits of electric cables with rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV)
IEC 60909‑0, Short-circuit currents in three-phase a.c. systems – Part 0: Calculation of currents
IEC 60949, Calculation of thermally permissible short-circuit currents, taking into account non-adiabatic heating effects
IEC 61140:2001, Protection against electric shock – Common aspects for installation and equipment
IEC 61534‑1, Powertrack systems – Part 1: General requirements
IEC 62305 (all parts), Protection against lightning
IEC 62305‑3:2006, Protection against lightning – Part 3: Physical damage to structures and life hazard
541.3Terms and definitions
For the purposes of this document, the terms and definitions of IEC 61140, together with the following definitions, apply.
Definitions used for earthing arrangements, protective conductors and protective bonding conductors are illustrated in Annex B and listed below:
541.3.1
conductive part of equipment which can be touched and which is not normally live, but which can become live when basic insulation fails
[SOURCE: IEC 60050‑826:2004, 826‑12‑10]
541.3.2
extraneous-conductive-part
conductive part not forming part of the electrical installation and liable to introduce an electric potential, generally the electric potential of a local earth
[SOURCE: IEC 60050‑825:2004, IEV 826‑12‑11]
541.3.3
conductive part, which may be embedded in the soil or in a specific conductive medium, e.g. concrete, in electrical contact with Earth
[SOURCE:
IEC 60050‑826:2004, 826‑13‑05
]
541.3.4
concrete-embedded foundation earth electrode
earth electrode embedded in concrete of a building foundation, generally in the form of a closed loop
[SOURCE:
IEC 60050‑826:2004, 826‑13‑08
]
541.3.5
soil-embedded foundation earth electrode
earth electrode buried in the soil under a building foundation, generally in the form of a closed loop
[SOURCE:
IEC 60050‑826:2004, 826‑13‑08
]
541.3.6
conductor provided for purposes of safety, for example protection against electric shock
[SOURCE: IEC 60050‑826:2004, 826‑13‑22]
Note 1 to entry: Examples of a protective conductor include a protective bonding conductor, a protective earthing conductor and an earthing conductor when used for protection against electric shock.
541.3.7
protective bonding conductor
protective conductor provided for protective-equipotential-bonding
[SOURCE: IEC 60050‑826:2004, 826‑13‑24]
541.3.8
conductor which provides a conductive path, or part of the conductive path, between a given point in a system or in an installation or in equipment and an earth-electrode network
[SOURCE: IEC 60050‑826:2004, 826‑13‑12]
Note 1 to entry: For the purposes of this part of IEC 60364, an earthing conductor is the conductor which connects the earth electrode to a point in the equipotential bonding system, usually the main earthing terminal.
541.3.9
terminal or busbar which is part of the earthing arrangement of an installation and enabling the electrical connection of a number of conductors for earthing purposes
[SOURCE: IEC 60050‑826:2004, 826‑13‑15]
541.3.10
protective earthing conductor
protective conductor provided for protective earthing
[SOURCE: IEC 60050‑826:2004, 826‑13‑23]
541.3.11
earthing a point or points in a system or in an installation or in equipment, for purposes other than electrical safety
[SOURCE: IEC 60050‑826:2004, IEV 826‑13‑10]
541.3.12
all the electrical connections and devices involved in the earthing of a system, installation or an equipment
[SOURCE: IEC 60050‑195:2004, 195‑02‑20]
542Earthing arrangements
542.1General requirements
542.1.1The earthing arrangements may be used jointly or separately for protective and functional purposes according to the requirements of the electrical installation. The requirements for protective purposes shall always take precedence.
542.1.2Where provided, earth electrodes within an installation shall be connected to the main earthing terminal using an earthing conductor.
NOTEAn installation does not need to have its own earth electrode.
542.1.3Where the supply to an installation is at high voltage, requirements concerning the earthing arrangements of the high voltage supply and of the low-voltage installation shall also comply with Clause 442 of IEC 60364‑4‑44:2007.
542.1.4The requirements for earthing arrangements are intended to provide a connection to earth which:
–
is reliable and suitable for the protective requirements of the installation;
–
can carry earth fault currents and protective conductor currents to earth without danger from thermal, thermo-mechanical and electromechanical stresses and from electric shock arising from these currents;
–
if relevant, is also suitable for functional requirements;
–
is suitable for the foreseeable external influences (see IEC 60364‑5‑51), e.g. mechanical stresses and corrosion.
542.1.5Consideration shall be given to the earthing arrangements where currents with high frequencies are expected to flow (see Clause 444 of IEC 60364‑4‑44:2007).
542.1.6Protection against electric shock, as stated in IEC 60364‑4‑41, shall not be adversely affected by any foreseeable change of the earth electrode resistance (e.g. due to corrosion, drying or freezing).
542.2Earth electrodes
542.2.1The type, materials and dimensions of earth electrodes shall be selected to withstand corrosion and to have adequate mechanical strength for the intended lifetime.
NOTE 1For corrosion, the following parameters may be considered: the soil pH at the site, soil resistivity, soil moisture, stray and leakage a.c. and d.c. current, chemical contamination, and proximity of dissimilar materials.
For materials commonly used for earth electrodes, the minimum sizes, from the point of view of corrosion and mechanical strength, when embedded in the soil or in concrete, shall be as specified in
Table 54.1.
NOTE 2The minimum thickness of protective coating is greater for vertical earth electrodes than for horizontal earth electrodes because of their greater exposure to mechanical stresses while being embedded.
If a lightning protection system is required, 5.4 of IEC 62305‑3:2006 applies.
Table 54.1 — Minimum size of commonly used earth electrodes, embedded in soil or concrete used to prevent corrosion and provide mechanical strength |
|---|
| Material and surface |
Shape |
Diameter |
Cross-sectional area |
Thickness |
Weight of coating |
Thickness of coating/ sheathing |
| mm |
mm2 |
mm |
g/m2 |
μm |
| Steel embedded in concrete (bare, hot galvanized or stainless) |
Round wire |
10 |
|
|
|
|
| Solid tape or strip |
|
75 |
3 |
|
|
| Steel hot-dip galvanizedc |
Stripb or shaped strip/plate – Solid plate – Lattice plate |
|
90 |
3 |
500 |
63 |
| Round rod installed vertically |
16 |
|
|
350 |
45 |
| Round wire installed horizontally |
10 |
|
|
350 |
45 |
| Pipe |
25 |
|
2 |
350 |
45 |
| Stranded (embedded in concrete) |
|
70 |
|
|
|
| Cross profile installed vertically |
|
(290) |
3 |
|
|
| Steel copper-sheathed |
Round rod installed vertically |
(15) |
|
|
|
2 000 |
| Steel with electro-deposited copper coating |
Round rod installed vertically |
14 |
|
|
|
250e |
| Round wire installed horizontally |
(8) |
|
|
|
70 |
| Strip installed horizontally |
|
90 |
3 |
|
70 |
| Stainless steela |
Stripb or shaped strip/plate |
|
90 |
3 |
|
|
| Round rod installed vertically |
16 |
|
|
|
|
| Round wire installed horizontally |
10 |
|
|
|
|
| Pipe |
25 |
|
2 |
|
|
| Copper |
Strip |
|
50 |
2 |
|
|
| Round wire installed horizontally |
|
(25)d 50 |
|
|
|
| Solid round rod installed vertically |
(12) 15 |
|
|
|
|
| Stranded wire |
1,7 for individual strands of wire |
(25)d 50 |
|
|
|
| Pipe |
20 |
|
2 |
|
|
| Solid plate |
|
|
(1,5) 2 |
|
|
| Lattice plate |
|
|
2 |
|
| |
|
542.2.2The efficacy of any earth electrode depends on its configuration and upon local soil conditions. One or more earth electrodes suitable for the soil conditions and the value of resistance to earth required shall be selected.
Annex D gives methods of estimation of earth electrode resistance.
542.2.3The following are examples of earth electrodes which may be used:
–
concrete-embedded foundation earth electrode;
NOTEFor more information see Annex C.
–
soil-embedded foundation earth electrode;
–
metallic electrode embedded directly in soil vertically or horizontally (e.g. rods, wires, tapes, pipes or plates);
–
metal sheath and other metal coverings of cables according to local conditions or requirements;
–
other suitable underground metalwork (e.g. pipes) according to local conditions or requirements;
–
welded metal reinforcement of concrete (except pre-stressed concrete) embedded in the earth.
542.2.4When selecting the type and embedded depth of an earth electrode, consideration shall be given to possible mechanical damage and to local conditions to minimize the effect of soil drying and freezing.
542.2.5Consideration shall be given to electrolytic corrosion when using different materials in an earthing arrangement. For external conductors (e.g. earthing conductor) connected to a concrete-embedded foundation earth electrode, the connection made from hot-dip galvanized steel shall not be embedded in the soil.
542.2.6The earthing arrangement shall not rely on a metallic pipe for flammable liquids or gases as the earth electrode and their buried length shall not be considered when dimensioning the earth electrode.
NOTEThis requirement does not preclude the protective equipotential bonding via the main earthing terminal (
541.3.9) of such pipes for compliance with
IEC 60364‑4‑41.
Where cathodic protection is applied and the exposed-conductive-part of an item of electrical equipment supplied by a TT system is directly connected to the pipe, a metallic pipe for flammable liquids or gases may act as the sole earth electrode for this specific equipment.
542.2.7Earth electrodes shall not be directly immersed in water of a stream, river, pond, lake or the like (see also
542.1.6).
542.2.8Where an earth electrode consists of parts that must be connected together, the connection shall be by exothermic welding, pressure connectors, clamps or other suitable mechanical connectors.
NOTEConnections made by a wrapped iron wire only are not suitable for protection purposes.
542.3Earthing conductors
542.3.1Earthing conductors shall comply with 543.1.1 or 543.1.2. Their cross-sectional area shall be not less than 6 mm
2 for copper or 50 mm
2 for steel. Where a bare earthing conductor is buried in the soil, its dimensions and characteristics shall also be in accordance with
Table 54.1.
Where no noticeable fault current is expected to flow through the earth electrode (e.g. in TN systems or IT systems), the earthing conductor may be dimensioned according to 544.1.
Aluminium conductors shall not be used as earthing conductors.
NOTEWhere a lightning protection system is connected to the earth electrode, the cross-sectional area of the earthing conductor should be at least 16 mm2 for copper (Cu) or 50 mm2 for iron (Fe) (see the IEC 62305 series).
542.3.2The connection of an earthing conductor to an earth electrode shall be soundly made and electrically satisfactory. The connection shall be by exothermic welding, pressure connectors, clamps or other suitable mechanical connectors. Mechanical connectors shall be installed in accordance with the manufacturer’s instructions. Where a clamp is used, it shall not damage the electrode or the earthing conductor.
Connection devices or fittings that depend solely on solder shall not be used independently, as they do not reliably provide adequate mechanical strength.
NOTEWhere vertical electrodes are installed, means may be provided to allow the inspection of the connection and the replacement of the vertical rod.
542.4Main earthing terminal
542.4.1In every installation where protective equipotential bonding is used, a main earthing terminal shall be provided and the following shall be connected to it:
–
protective bonding conductors;
–
functional earthing conductors, if relevant.
NOTE 1It is not intended to connect every individual protective conductor directly to the main earthing terminal where they are connected to this terminal by other protective conductors.
NOTE 2The main earthing terminal of the building can generally be used for functional earthing purposes. For information technology purposes, it is then regarded as the connection point to the earth.
Where more than one earthing terminal is provided, they shall be interconnected.
542.4.2Each conductor connected to the main earthing terminal shall be able to be disconnected individually. This connection shall be reliable and such that it can only be disconnected by means of a tool.
NOTEDisconnection means may conveniently be combined with the main earthing terminal, to permit measurement of the resistance of the earth electrode.