FOREWORD
1 Scope
2 Normative references
3 Terms, definitions, symbols and abbreviated terms
 3.1 General
 3.2 Alphabetical index of terms
 3.3 Terms and definitions concerning contactors
 3.4 Terms and definitions of the functions of starters
 3.5 Terms and definitions concerning starters
 3.6 Terms and definitions concerning characteristic quantities
 3.7 Terms and definitions concerning safety aspects
 3.8 Terms and definitions concerning electric motor characteristics
 3.9 Symbols and abbreviated terms
4 Classification
5 Characteristics of contactors and starters
 5.1 Summary of characteristics
 5.2 Type of equipment
  5.2.1 Kind of equipment
  5.2.2 Number of poles
  5.2.3 Kind of current (AC or DC)
  5.2.4 Interrupting medium (air, oil, gas, vacuum, etc.)
  5.2.5 Operating conditions of the equipment
  5.2.6 Methods of overload protection of motors
 5.3 Rated and limiting values for main circuits
  5.3.1 Rated voltages
  5.3.2 Currents or powers
  5.3.3 Rated frequency
  5.3.4 Rated duties
  5.3.5 Normal load and overload characteristics
  5.3.6 Short-circuit characteristics
  5.3.7 Pole impedance of a contactor (Z) or starter
 5.4 Utilization category
  5.4.1 General
  5.4.2 Assignment of utilization categories based on the results of tests
 5.5 Control circuits
 5.6 Auxiliary circuits
 5.7 Characteristics of relay and release of overload relays and of motor protective switching device (MPSD)
  5.7.1 Summary of characteristics
  5.7.2 Types of relay or release
  5.7.3 Characteristic values
  5.7.4 Designation and current settings of overload relays
  5.7.5 Time-current characteristics of overload relays
  5.7.6 Influence of ambient air temperature
 5.8 Co-ordination with short-circuit protective devices
 5.9 Void
 5.10 Types and characteristics of automatic change-over devices and automatic acceleration control devices
  5.10.1 Types
  5.10.2 Characteristics
 5.11 Types and characteristics of auto-transformers for two-step auto-transformer starters
 5.12 Types and characteristics of starting resistors for rheostatic rotor starters
6 Product information
 6.1 Nature of information
  6.1.1 Identification
  6.1.2 Characteristics, basic rated values and utilization
 6.2 Marking
 6.3 Instructions for installation, operation, maintenance, decommissioning and dismantling
 6.4 Environmental information
 6.5 Instruction for equipment capable to be reused, repaired and upgraded
7 Normal service, mounting and transport conditions
8 Constructional and performance requirements
 8.1 Constructional requirements
  8.1.1 General
  8.1.2 Materials
  8.1.3 Current-carrying parts and their connections
  8.1.4 Clearances and creepage distances
  8.1.5 Actuator
  8.1.6 Indication of the contact position
  8.1.7 Additional requirements for equipment suitable for isolation
  8.1.8 Terminals
  8.1.9 Additional requirements for equipment provided with a neutral pole
  8.1.10 Provisions for protective earthing
  8.1.11 Enclosures for equipment
  8.1.12 Degrees of protection of enclosed equipment
  8.1.13 Conduit pull-out, torque and bending with metallic conduits
  8.1.14 Limited energy source
  8.1.15 Stored charge energy circuit
  8.1.16 Fault and abnormal conditions
  8.1.17 Short-circuit and overload protection of ports
  8.1.18 Use of voltage transient limiting device
 8.2 Performance requirements
  8.2.1 Operating conditions
  8.2.2 Temperature-rise
  8.2.3 Dielectric properties
  8.2.4 Normal load and overload performance requirements
  8.2.5 Co-ordination with short-circuit protective devices
 8.3 Electromagnetic compatibility (EMC)
  8.3.1 General
  8.3.2 Immunity
  8.3.3 Emission
 8.4 Embedded software
 8.5 Security
9 Tests
 9.1 Kinds of test
  9.1.1 General
  9.1.2 Type tests
  9.1.3 Routine tests
  9.1.4 Sampling tests
  9.1.5 Special tests
 9.2 Compliance with constructional requirements
  9.2.1 General
  9.2.2 Electrical performance of screwless-type clamping units
  9.2.3 Ageing test for screwless-type clamping units
  9.2.4 Limited energy source test
  9.2.5 Breakdown of components
  9.2.6 Wire flexing test
 9.3 Compliance with performance requirements
  9.3.1 Test sequences
  9.3.2 General test conditions
  9.3.3 Performance under no load, normal load and overload conditions
  9.3.4 Performance under short-circuit conditions
  9.3.5 Overload current withstand capability of contactors and IMPSDs
  9.3.6 Routine tests and sampling tests
 9.4 EMC tests
  9.4.1 General
  9.4.2 Immunity
  9.4.3 Emission
Annex A (normative) Marking and identification of terminals of contactors, starters and associated overload relays
Annex B (normative) Special tests
Annex C (informative) Electric motor evolutions and motor starting methods
Annex D (informative) Items subject to agreement between manufacturer and user
Annex E (Void)
Annex F (normative) Requirements for auxiliary contact linked with power contact (mirror contact)
Annex G (informative) Rated operational currents and rated operational powers of switching devices for electrical motors
Annex H (normative) Extended functions to electronic overload relays
Annex I (informative) AC-1 contactors for use with semiconductor controlled motor load
Annex J (Void)
Annex K (normative) Procedure to determine data for electromechanical contactors used in functional safety applications
Annex L (normative) Assessment procedure for electromechanical overload protection used in safety applications and especially in explosive atmospheres
Annex M (normative) DC contactors for use in photovoltaic (PV) applications
Annex N (normative) Additional requirements and tests for equipment with protective separation
Annex O (normative) Load monitoring indicators
Annex P (normative) Short-circuit breaking tests of MPSD
Bibliography
30mm
20mm
15mm
15mm
10mm
17mm
Gulf StandardGSO IEC 60947-4-1:2024
Gulf StandardGSO IEC 60947-4-1:2024
GSO IEC 60947-4-1:2024Gulf Standard
GSO IEC 60947-4-1:2024
IEC 60947-4-1:2023
مواصفة قياسية خليجية
معدات القطع والوصل والتحكم للجهد المنخفض – الجزء 4-1 : الملامسات وأجهزة بدء المحركات - الملامسات الكهروميكانيكية وأجهزة بدء المحركات.
Gulf Standard
Low-voltage switchgear and controlgear - Part 4-1: Contactors and motor-starters - Electromechanical contactors and motor-starters
ICS:
29.120.99 ; 29.130.20

هذه الوثيقة محمية بالقانون
COPYRIGHT PROTECTED DOCUMENT
جميع الحقوق محفوظة لهيئة لتقييس لدول مجلس التعاون لدول الخليج العربية.
ما لم ينص على خلاف ذلك، لا يجوز إعادة إنتاج أي جزء من هذا المنشور أو استخدامه بأي شكل آخر أو بأي وسيلة، إلكترونية أو ميكانيكية، بما في ذلك التصوير، أو النشر على الإنترنت أو الإنترانت، دون إذن كتابي مسبق من هيئة التقييس لدول مجلس التعاون لدول الخليج العربية على العنوان أدناه أو الدول الأعضاء في الهيئة داخل بلدانهم.
All rights reserved to GCC Standardization Organization (GSO). Unless otherwise specified, no part of this publication may be reproduced or utilized otherwise in any form or by any means, electronic or mechanical, including photocopying, or posting on the internet or an intranet, without prior written permission. Permission can be requested from either GSO at the address below or GSO's member body in the country of the requester.
Outreach Dept, Knowledge Management Section
GCC Standardization Organization (GSO)
P.O.Box: 85245 Riyadh 12511
Kingdom of Saudi Arabia
إدارة التواصل، قسم إدارة المعرفة
هيئة التقييس لدول مجلس التعاون لدول الخليج العربية (GSO)
ص. ب: 85245 الرياض 12511
المملكة العربية السعودية
Tel: +966115208000 :هاتف
Fax: +966115208010 :فاكس
E-Mail: csc@gso.org.sa :بريد إلكتروني
Website: www.gso.org.sa :موقع ويب
30mm
20mm
15mm
15mm
10mm
17mm

Gulf StandardGSO IEC 60947-4-1:2024
Gulf StandardGSO IEC 60947-4-1:2024
GSO IEC 60947-4-1:2024Gulf Standard

Gulf Foreword

GCC Standardization Organization (GSO) is a regional organization which consists of the national standardization bodies of GCC member states. One of GSO main functions is to issue gulf standards and technical regulations through specialized technical committees.
GSO Technical Council in its meeting number (59) held on 10/04/1446 H, which corresponds to 14/10/2024, has approved the update of Gulf Standard GSO IEC 60947-4-1:2024 titled "Low-voltage switchgear and controlgear - Part 4-1: Contactors and motor-starters - Electromechanical contactors and motor-starters" in English language which was studied and adopted by endorsement from International Electrotechnical Commission Standard IEC 60947-4-1:2023 through the technical program of GSO Technical Committee for Electrical and Electronic Products (TC03) in YEMEN schedule . This document will cancel and replace the Gulf Standard GSO IEC 60947-4-1:2016. This document will cancel and replace the Gulf Standard(s) GSO IEC 60947-4-1:2016.
تقديم خليجي
هيئة التقييس لدول مجلس التعاون لدول الخليج العربية هيئة إقليمية تضم في عضويتها أجهزة التقييس الوطنية في الدول الأعضاء ، ومن مهام الهيئة إعداد المواصفات القياسية واللوائح الفنية الخليجية بواسطة لجان فنية متخصصة.
قرر المجلس الفني لهيئة التقييس لدول مجلس التعاون لدول الخليج العربية في الاجتماع الـ (59) بتاريخ 1446/04/10 هـ ،الموافق 2024/10/14م اعتماد تحديث المواصفة القياسية الخليجية رقم GSO IEC 60947-4-1:2024 وعنوانها "معدات القطع والوصل والتحكم للجهد المنخفض – الجزء 4-1 : الملامسات وأجهزة بدء المحركات - الملامسات الكهروميكانيكية وأجهزة بدء المحركات." باللغة الانجليزية التي تم دراستها وتبنيها بالمصادقة عن اللجنة الدولية الكهروتقنية رقم IEC 60947-4-1:2023 ضمن برنامج عمل اللجنة الفنية الخليجية للمواصفات الكهربائية والإلكترونية (TC03) المدرجة في خطة الجمهورية اليمنية . على أن تلغي وتحل محل المواصفة القياسية رقم GSO IEC 60947-4-1:2016 . على أن تلغي وتحل محل المواصفة القياسية GSO IEC 60947-4-1:2016 .
30mm
20mm
15mm
15mm
10mm
17mm
Gulf StandardGSO IEC 60947-4-1:2024
Gulf StandardGSO IEC 60947-4-1:2024
Gulf StandardGSO IEC 60947-4-1:2024
GSO IEC 60947-4-1:2024Gulf Standard
IEC 60947-4-1

INTERNATIONAL

STANDARD

Edition 5.0  2023-11
Low-voltage switchgear and controlgear –
Part 4-1: Contactors and motor-starters – Electromechanical contactors and motor-starters
IEC 60947-4-1:2023 ED5
30mm
20mm
15mm
15mm
10mm
17mm
Gulf StandardGSO IEC 60947-4-1:2024
Gulf StandardGSO IEC 60947-4-1:2024
Gulf StandardGSO IEC 60947-4-1:2024
GSO IEC 60947-4-1:2024Gulf Standard
THIS PUBLICATION IS COPYRIGHT PROTECTEDCopyright © 2023 IEC, Geneva, Switzerland
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form or by any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from either IEC or IEC's member National Committee in the country of the requester. If you have any questions about IEC copyright or have an enquiry about obtaining additional rights to this publication, please contact the address below or your local IEC member National Committee for further information.
IEC Secretariat3, rue de VarembéCH-1211 Geneva 20Switzerland Tel.: +41 22 919 02 11 info@iec.ch www.iec.ch
About the IEC The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes International Standards for all electrical, electronic and related technologies. About IEC publications The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the latest edition, a corrigendum or an amendment might have been published.
IEC publications search - webstore.iec.ch/advsearchform The advanced search enables to find IEC publications by a variety of criteria (reference number, text, technical committee, ...). It also gives information on projects, replaced and withdrawn publications. IEC Just Published - webstore.iec.ch/justpublished Stay up to date on all new IEC publications. Just Published details all new publications released. Available online and once a month by email. IEC Customer Service Centre - webstore.iec.ch/csc If you wish to give us your feedback on this publication or need further assistance, please contact the Customer Service Centre: sales@iec.ch .   IEC Products & Services Portal - products.iec.ch Discover our powerful search engine and read freely all the publications previews. With a subscription you will always have access to up to date content tailored to your needs. Electropedia - www.electropedia.org The world's leading online dictionary on electrotechnology, containing more than 22 300 terminological entries in English and French, with equivalent terms in 19 additional languages. Also known as the International Electrotechnical Vocabulary (IEV) online.
30mm
20mm
15mm
15mm
10mm
17mm
Gulf StandardGSO IEC 60947-4-1:2024
Gulf StandardGSO IEC 60947-4-1:2024
Gulf StandardGSO IEC 60947-4-1:2024
GSO IEC 60947-4-1:2024Gulf Standard
IEC 60947-4-1

INTERNATIONAL

STANDARD

Edition 5.0  2023-11
Low-voltage switchgear and controlgear –
Part 4-1: Contactors and motor-starters – Electromechanical contactors and motor-starters

INTERNATIONAL

ELECTROTECHNCIAL

COMMISSION


ICS 29.120.99, 29.130.20ISBN 9782832277737Warning! Make sure that you obtained this publication from an authorized distributor.© Registered trademark of the International Electrotechnical Commission
30mm
20mm
15mm
15mm
10mm
17mm

Gulf StandardGSO IEC 60947-4-1:2024
Gulf StandardGSO IEC 60947-4-1:2024
Gulf StandardGSO IEC 60947-4-1:2024
GSO IEC 60947-4-1:2024Gulf Standard
CONTENTS
INTERNATIONAL ELECTROTECHNICAL COMMISSION
International StandardIEC 60947-4-1:2023 ED5
Low-voltage switchgear and controlgear - Part 4-1: Contactors and motor-starters - Electromechanical contactors and motor-starters

FOREWORD

1)
The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising all national electrotechnical committees (IEC National Committees). The object of IEC is to promote international co-operation on all questions concerning standardization in the electrical and electronic fields. To this end and in addition to other activities, IEC publishes International Standards, Technical Specifications, Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested in the subject dealt with may participate in this preparatory work. International, governmental and non-governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely with the International Organization for Standardization (ISO) in accordance with conditions determined by agreement between the two organizations.
2)
The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international consensus of opinion on the relevant subjects since each technical committee has representation from all interested IEC National Committees.
3)
IEC Publications have the form of recommendations for international use and are accepted by IEC National Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any misinterpretation by any end user.
4)
In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications transparently to the maximum extent possible in their national and regional publications. Any divergence between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in the latter.
5)
IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any services carried out by independent certification bodies.
6)
All users should ensure that they have the latest edition of this publication.
7)
No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and members of its technical committees and IEC National Committees for any personal injury, property damage or other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC Publications.
8)
Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is indispensable for the correct application of this publication.
9)
IEC draws attention to the possibility that the implementation of this document may involve the use of (a) patent(s). IEC takes no position concerning the evidence, validity or applicability of any claimed patent rights in respect thereof. As of the date of publication of this document, IEC had not received notice of (a) patent(s), which may be required to implement this document. However, implementers are cautioned that this may not represent the latest information, which may be obtained from the patent database available at https://patents.iec.ch. IEC shall not be held responsible for identifying any or all such patent rights.
IEC 60947-4-1 has been prepared by subcommittee 121A: Low-voltage switchgear and controlgear, of IEC technical committee 121: Switchgear and controlgear and their assemblies for low voltage. It is an International Standard.
This fifth edition cancels and replaces the fourth edition published in 2018. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous edition:
a)
objective in the scope;
b)
instantaneous only motor protective switching device IMPSD (3.5.33);
c)
kinds of equipment (5.2.1);
d)
methods of overload protection of motors (5.2.6);
e)
adoption of the AC-7d from IEC 61095:2023 (in 5.4.2);
f)
separately mounted overload relay of a starter (in 5.7.3 b));
g)
starter and contactor suitable for use downstream to basic drive module (6.1.2 w));
h)
reference to IEC TS 63058 for environmental aspects (in 6.4);
i)
wiring subject to movement (in 8.1.3);
j)
use of voltage transient limiting device (8.1.18);
k)
accessible parts subject to temperature limits (in 8.2.2.3);
l)
reference to Annex X of IEC 60947-1:2020 for the co-ordination of MPSD with SCPD (8.2.5.4);
m)
reference to IEC TR 63216 with different EMC environments (8.3.1);
n)
reference to IEC TR 63201 for the embedded software design (8.4);
o)
reference to IEC TS 63208 for cybersecurity aspects (8.5);
p)
update and completion of the measurement method of the power consumption of the electromagnet (9.3.3.2.1.2);
q)
update of Annex C including rational about AC-3e;
r)
determination of the critical load current for photovoltaic applications (M.8.7).
The text of this International Standard is based on the following documents:
Draft Report on voting
121A/571/FDIS 121A/580/RVD
Full information on the voting for its approval can be found in the report on voting indicated in the above table.
The language used for the development of this International Standard is English.
This document was drafted in accordance with ISO/IEC Directives, Part 2, and developed in accordance with ISO/IEC Directives, Part 1 and ISO/IEC Directives, IEC Supplement, available at www.iec.ch/members_experts/refdocs. The main document types developed by IEC are described in greater detail at www.iec.ch/publications.
A list of all parts of the IEC 60947 series can be found, under the general title Low-voltage switchgear and controlgear, on the IEC website.
This document shall be read in conjunction with IEC 60947-1:2020, Low voltage switchgear and controlgear - Part 1: General rules. The provisions of the general rules are applicable to this document, where specifically called for.
The provisions of the general rules dealt with IEC 60947-1 are applicable to this part of IEC 60947 series where specifically called for. Clauses and subclauses, tables, figures and annexes of the general rules thus applicable are identified by reference to IEC 60947-1:2020. For example, 5.3.4.1 of IEC 60947-1:2020, Table 4 of IEC 60947-1:2020, or Annex A of IEC 60947-1:2020.
The committee has decided that the contents of this document will remain unchanged until the stability date indicated on the IEC website under webstore.iec.ch in the data related to the specific document. At this date, the document will be
•
reconfirmed,
•
withdrawn,
•
replaced by a revised edition, or
•
amended.
IMPORTANTThe "colour inside" logo on the cover page of this document indicates that it contains colours which are considered to be useful for the correct understanding of its contents. Users should therefore print this document using a colour printer.
30mm
20mm
15mm
15mm
10mm
17mm

Gulf StandardGSO IEC 60947-4-1:2024
Gulf StandardGSO IEC 60947-4-1:2024
Gulf StandardGSO IEC 60947-4-1:2024
GSO IEC 60947-4-1:2024Gulf Standard
International StandardIEC 60947-4-1:2023 ED5
Low-voltage switchgear and controlgear - Part 4-1: Contactors and motor-starters - Electromechanical contactors and motor-starters

1Scope

This part of IEC 60947 is applicable to the following equipment:
-
electromechanical contactors and starters including motor protective switching devices (MPSD and IMPSD);
-
actuators of contactor relays;
-
contacts dedicated exclusively to the coil circuit of the contactor or the contactor relay;
-
dedicated accessories (e.g. dedicated wiring, dedicated latch accessory);
intended to be connected to distribution circuits, motors circuits and other load circuits, the rated voltage of which does not exceed 1 000 V AC or 1 500 V DC.
This document does not apply to:
-
starters for DC motors0F;
-
auxiliary contacts of contactors and contacts of contactor relays. These are covered by IEC 60947-5-1;
-
the short-circuit protective device integrated within starters, other than MPSDs. This is covered by IEC 60947-2 and IEC 60947-3;
-
motor overload protection function performed by control units for built-in thermal protection (PTC). They are covered by IEC 60947-8;
-
the use of the equipment with additional measures within explosive atmospheres. These are given in IEC 60079 series;
The objective of this document is to state:
•
the characteristics and composition of the equipment (Clause 5);
•
the conditions applicable to the equipment with reference to:
-
its operation (5.2.5) and protection functions (5.2.6, 5.7, 5.8),
-
its intended environments (6.5, 8.3.1) and applications (5.4, Annex C, Annex D, Annex G, Annex H, Annex I, Annex M, Annex O) including safety applications (Annex F, Annex K, Annex L),
-
its construction and performance (Clause 8) including requirements to reduce risks of electric shock, thermal hazard, energy hazard, fire hazard and mechanical hazard, reasonably foreseeable misuse, electromagnetic compatibility (EMC) issues, software errors and security issues;
•
the tests intended for confirming that these conditions have been met, and the methods to be adopted for these tests (Clause 9);
•
the information to be included with the equipment or in the product documentation (Clause 6).

2Normative references

The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.
IEC 60034-1:2022, Rotating electrical machines - Part 1: Rating and performance
IEC 60034-12:2016, Rotating electrical machines - Part 12: Starting performance of single-speed three-phase cage induction motors
IEC 60034-30-1:2014, Rotating electrical machines - Part 30-1: Efficiency classes of line operated AC motors (IE code)
IEC 60068-2-14:2023, Environmental testing - Part 2-14: Tests - Test N: Change of temperature
IEC 60079-14, Explosive atmospheres - Part 14: Electrical installations design, selection and erection
IEC 60085:2007, Electrical insulation - Thermal evaluation and designation
IEC 60364-1:2005, Low-voltage electrical installations - Part 1: Fundamental principles, assessment of general characteristics, definitions
IEC 60715:2017, Dimensions of low-voltage switchgear and controlgear - Standardized mounting on rails for mechanical support of switchgear, controlgear and accessories
IEC 60730-1, Automatic electrical controls - Part 1: General requirements
IEC 60947-1:2020, Low-voltage switchgear and controlgear - Part 1: General rules
IEC 60947-2:2016, Low-voltage switchgear and controlgear - Part 2: Circuit-breakers
IEC 60947-5-1:2016, Low-voltage switchgear and controlgear - Part 5-1: Control circuit devices and switching elements - Electromechanical control circuit devices
IEC 61051-2, Varistors for use in electronic equipment - Part 2: Sectional specification for surge suppression varistors
IEC 61095:2023, Electromechanical contactors for household and similar purposes
IEC 61140:2016, Protection against electric shock - Common aspects for installation and equipment
IEC 61439 (all parts), Low-voltage switchgear and controlgear assemblies
IEC 61643-331, Components for low-voltage surge protection - Part 331: Performance requirements and test methods for metal oxide varistors (MOV)
IEC 61800-5-1:2022, Adjustable speed electrical power drive systems - Part 5-1: Safety requirements - Electrical, thermal and energy
IEC 61810-1, Electromechanical elementary relays - Part 1: General and safety requirements
IEC TS 63058, Switchgear and controlgear and their assemblies for low voltage - Environmental aspects
IEC TS 63208, Low-voltage switchgear and controlgear - Security aspects
IEC TR 63216:2019, Low-voltage switchgear and controlgear - Electromagnetic compatibility assessment for switchgear and controlgear and their assemblies
CISPR 11:2015, Industrial, scientific and medical equipment - Radio-frequency disturbance characteristics - Limits and methods of measurement
CISPR 11:2015/AMD1:2016
CISPR 11:2015/AMD2:2019
ISO 2859-1:1999, Sampling procedures for inspection by attributes - Part 1: Sampling schemes indexed by acceptance quality limit (AQL) for lot-by-lot inspection
ISO 3864-2, Graphical symbols - Safety colours and safety signs - Part 2: Design principles for product safety labels

3Terms, definitions, symbols and abbreviated terms

3.1General

For the purposes of this document, the terms and definitions of Clause 3 of IEC 60947-1:2020, as well as the following terms, definitions, symbols and abbreviated terms apply.
ISO and IEC maintain terminology databases for use in standardization at the following addresses:
•
IEC Electropedia: available at https://www.electropedia.org/
•
ISO Online browsing platform: available at https://www.iso.org/obp

3.2Alphabetical index of terms

Reference
A
abnormal operating condition 3.7.1
accessible part 3.7.2
auto-transformer starter 3.5.4.2
auto-transformer 3.5.4.3
B
basic drive module (abbreviation: BDM) 3.5.36
C
closed transition (with an auto-transformer starter or star-delta starter) 3.5.23
combination starter 3.5.7
combination switching device 3.5.27
conventional prospective current "r" 3.6.9
CO operation 3.6.3
contactor (mechanical) 3.3.1
D
dedicated wiring accessory 3.5.34
direct-on-line starter 3.5.2
E
electromagnetic contactor 3.3.2
electromagnetic starter 3.5.9
electronically controlled electromagnet 3.3.8
electro-pneumatic contactor 3.3.4
electro-pneumatic starter 3.5.12
G
galvanic opening (of a circuit) 3.6.13
galvanic separation 3.6.14
H
hazardous-live-part 3.7.4
holding power (of a contactor) 3.3.9
hot functional surface 3.7.10
I
I2t characteristic of a circuit-breaker or a MPSD 3.6.10
Icd current 3.6.5
inching (jogging) 3.5.24
inhibit time 3.5.30
instantaneous only motor protective switching device (abbreviation: IMPSD) 3.5.33
J
jam relay (or release) 3.5.29
L
latch accessory 3.5.35
latched contactor 3.3.5
live-part 3.7.3
limited energy source 3.7.5
M
manual starter 3.5.8
mirror contact 3.7.11
motor management starter 3.5.31
motor-operated starter 3.5.10
motor protective switching device (abbreviation: MPSD) 3.5.32
motor starter 3.5.1
N
n-step starter 3.5.15
O
O operation 3.6.4
open transition (with an auto-transformer starter or star-delta starter) 3.5.22
overload current setting (abbreviation: Ir) 3.6.12
P
phase loss sensitive overload relay or release 3.5.18
pick-up power (of a contactor) 3.3.10
plugging 3.5.25
pneumatic contactor 3.3.3
pneumatic starter 3.5.11
position of rest (of a contactor) 3.3.7
product documentation 3.6.1
protected starter 3.5.6
protected switching device 3.5.26
protective impedance 3.7.6
R
rated instantaneous short-circuit current setting (abbreviation: Ii) 3.6.11
rated voltage pulse slope (abbreviation: dV/dt) 3.6.16
reasonably foreseeable misuse 3.7.7
recurring peak voltage 3.6.15
reduced voltage starter 3.5.4
resetting time 3.6.8
reversing starter 3.5.3
rheostatic rotor starter 3.5.5.2
rheostatic starter 3.5.5
rheostatic stator starter 3.5.5.1
S
separately mounted overload relay 3.5.17
single fault condition 3.7.8
single-step starter 3.5.13
stall relay (or release) 3.5.28
star-delta starter 3.5.4.1
starter 3.5.1
starting time (of a rheostatic starter) 3.5.20
starting time (of an auto-transformer starter) 3.5.21
T
transient recovery voltage (abbreviation: TRV) 3.6.2
two-step starter 3.5.14
U
under-current relay or release 3.5.19
V
vacuum contactor (or starter) 3.3.6

3.3Terms and definitions concerning contactors

3.3.1
mechanical contactor
contactor
mechanical switching device having only one position of rest, operated otherwise than by hand, capable of making, carrying and breaking currents under normal circuit conditions including operating overload conditions
Note 1 to entry: Mechanical contactors can be designated according to the method by which the force for closing the main contacts is provided.
Note 2 to entry: The term "operated otherwise than by hand" means that the device is intended to be controlled and kept in working position from one or more external supplies.
Note 3 to entry: In French, a contactor the main contacts of which are closed in the position of rest is usually called a "rupteur". The word "rupteur" has no equivalent in the English language.
Note 4 to entry: A contactor is usually intended to operate frequently.
Note 5 to entry: A mechanical contactor can provide a galvanic opening (3.6.13) but is not suitable for isolation unless the additional requirements defined under 8.1.7 are fulfilled. In this case the equipment can be marked in accordance with IEC 60417-6169-1 "Disconnector; isolator" (2012-08).
[SOURCE: IEC 60050-441:1984, 441-14-33, modified - Term“contactor” added as synonymous; "may" replaced by "can" in Note 1 to entry; Notes to entry 2 to 5 have been added.]
3.3.2
electromagnetic contactor
contactor in which the force for closing the normally open main contacts or opening the normally closed main contacts is provided by an electromagnet
Note 1 to entry: The electromagnet can be electronically controlled.
3.3.3
pneumatic contactor
contactor in which the force for closing the normally open main contacts or opening the normally closed main contacts is provided by a device using compressed air, without the use of electrical means
3.3.4
electro-pneumatic contactor
contactor in which the force for closing the normally open main contacts or opening the normally closed main contacts is provided by a device using compressed air under the control of electrically operated valves
3.3.5
latched contactor
contactor, the moving elements of which are prevented by means of a latching arrangement from returning to the position of rest when the operating means are de-energized
Note 1 to entry: The latching, and the release of the latching, can be mechanical, electromagnetic, pneumatic, etc.
Note 2 to entry: Because of the latching, the latched contactor actually acquires a second position of rest and, according to the definition of a contactor, it is not, strictly speaking, a contactor. However, since the latched contactor in both its utilization and its design is more closely related to contactors in general than to any other classification of switching device, it is considered proper to require that it complies with the specifications for contactors wherever they are appropriate.
[SOURCE: IEC 60050-441:1984, 441-14-34, modified - "may" replaced by "can" in Note 1 to entry.]
3.3.6
vacuum contactor
contactor in which the main contacts open and close within a highly evacuated envelope
3.3.7
position of rest
<contactor> position which the moving elements of the contactor take up when its electromagnet or its compressed-air device is not energized
[SOURCE: IEC 60050-441:1984, 441-16-24]
3.3.8
electronically controlled electromagnet
electromagnet in which the coil is controlled by a circuit with active electronic elements
3.3.9
holding power
<contactor> power needed to maintain the operation of the electromagnet
3.3.10
pick-up power
<contactor> power needed to operate the contactor from the de-energized state to the energized state

3.4Terms and definitions of the functions of starters

3.4.1
switching
<motor starter> capability to make and break the current of a motor in normal operation according to the appropriate motor load utilization category
3.4.2
overload protection
<motor starter> detection of the overload condition of a motor intended to control mechanically or electrically the opening of the switching function of the starter
3.4.3
electromechanical overload protection
protection of a rotating electrical machine in case of excessive temperatures resulting from certain conditions of overload by means of thermo mechanical detection that initiate the interruption of the motor load circuit
Note 1 to entry: Electromechanical overload protection is typically provided by thermal overload relays or motor protective switching devices (MPSD).
3.4.4
isolating
<motor starter> ability to provide in an indicated open position adequate isolation between the motor circuits and the supply circuits
3.4.5
electronic overload relay with control functions
multipole electronic relay with motor control operations through its inputs and outputs
Note 1 to entry: Example of control functions: reversing control, two speed control, star-delta control, etc.
3.4.6
electronic overload relay with under-voltage restarting function
electronic relay which operates when the voltage applied to the main circuit or control circuit is reduced below a predetermined value and automatically resets (with or without time delay) when the voltage is recovered
3.4.7
electronic overload relay with main circuit undervoltage restarting function
electronic overload relay with under-voltage restarting function monitoring only the main circuit
3.4.8
electronic overload relay with control circuit undervoltage restarting function
electronic overload relay with under-voltage restarting function monitoring only the control circuit
Note 1 to entry: The automatic restarting function can be de-activated.

3.5Terms and definitions concerning starters

3.5.1
motor starter
starter
combination of all the switching means necessary to start and stop a motor in combination with suitable overload protection
[SOURCE: IEC 60050-441:1984, 441-14-38, modified - "motor starter" added as the first term and Note 1 to entry has been deleted.]
3.5.2
direct-on-line starter
starter which connects the line voltage across the motor terminals in one step
[SOURCE: IEC 60050-441:1984, 441-14-40]
3.5.3
reversing starter
starter intended to cause the motor to reverse the direction of rotation by reversing the motor primary connections when the motor is not running
Note 1 to entry: An application where reversing the motor primary connections while the motor is running is called plugging (see 3.5.25).
3.5.4
reduced voltage starter
starter which connects the line voltage across the motor terminals in more than one step or by gradually increasing the voltage applied to the terminals
3.5.4.1
star-delta starter
starter for a three-phase induction motor such that in the starting position the stator windings are connected in star and in the final running position they are connected in delta
[SOURCE: IEC 60050-441:1984, 441-14-44]
3.5.4.2
auto-transformer starter
starter for an induction motor which uses for starting one or more reduced voltages derived from an auto-transformer
[SOURCE: IEC 60050-441:1984, 441-14-45]
3.5.4.3
auto-transformer
transformer in which at least two windings have a common part
[SOURCE: IEC 60050-421:1990, 421-01-11]
3.5.5
rheostatic starter
starter utilizing one or several resistors for obtaining, during starting, stated motor torque characteristics and for limiting the current
Note 1 to entry: A rheostatic starter generally consists of three basic parts which can be supplied either as a composite unit or as separate units to be connected at the place of utilization:
-
the mechanical switching devices for supplying the stator (generally associated with an overload protective device);
-
the resistor(s) inserted in the stator or rotor circuit;
-
the mechanical switching devices for cutting out the resistor(s) successively.
Note 2 to entry: It applies also to starters for two directions of rotation when reversal of connections is made with the motor stopped.
[SOURCE: IEC 60050-441:1984, 441-14-42, modified - Notes to entry have been added]
3.5.5.1
rheostatic stator starter
rheostatic starter for a squirrel cage motor which, during the starting period, cuts out successively one or several resistors previously provided in the stator circuit
3.5.5.2
rheostatic rotor starter
rheostatic starter for an asynchronous wound-rotor motor which, during the starting period, cuts out successively one or several resistors previously provided in the rotor circuit
[SOURCE: IEC 60050-441:1984, 441-14-43]
3.5.6
protected starter
equipment consisting of a starter, a manually-operated switching device and a short-circuit protective device, rated as a unit by the manufacturer
Note 1 to entry: The protected starter can be enclosed.
Note 2 to entry: In the context of this document, the term "manufacturer" means any person, company or organization with ultimate responsibility as follows:
-
to verify compliance with the appropriate standard;
-
to provide the equipment information according to Clause 6.
Note 3 to entry: A manually protected starter as one unit can be a MPSD.
3.5.7
combination starter
equipment consisting of a protected starter incorporating an isolating function
Note 1 to entry: Also called "combination motor controller".
Note 2 to entry: See Figure C.7.
3.5.8
manual starter
starter in which the force for closing the main contacts is provided exclusively by manual energy
[SOURCE: IEC 60050-441:1984, 441-14-39]
3.5.9
electromagnetic starter
starter in which the force for closing the main contacts is provided by an electromagnet
3.5.10
motor-operated starter
starter in which the force for closing the main contacts is provided by an electric motor
3.5.11
pneumatic starter
starter in which the force for closing the main contacts is provided by using compressed air, without the use of electrical means
3.5.12
electro-pneumatic starter
starter in which the force for closing the main contacts is provided by using compressed air under the control of electrically operated valves
3.5.13
single-step starter
starter in which there is no intermediate accelerating position between the OFF and ON positions
Note 1 to entry: This starter is a direct-on-line starter.
3.5.14
two-step starter
starter in which there is only one intermediate accelerating position between the OFF and ON positions
EXAMPLE        A star-delta starter is a two-step starter.
3.5.15
n-step starter
starter in which there are (n-1) intermediate accelerating positions between the OFF and full ON positions
EXAMPLE        A three-step rheostatic starter has two sections of resistors used for starting.
[SOURCE: IEC 60050-441:1984, 441-14-41, modified - "OFF" and "ON" in capital; Example added]
3.5.16
vacuum starter
starter in which the main contacts open and close within a highly evacuated envelope
3.5.17
separately mounted overload relay
overload relays not exclusively dedicated to a switching device
3.5.18
phase loss sensitive overload relay
phase loss sensitive overload release
multipole overload relay or release which operates in the case of overload and also in case of loss of phase in accordance with specified requirements
3.5.19
under-current relay
under-current relay release
measuring relay or release which operates automatically when the current through it is reduced below a predetermined value
3.5.20
starting time
<rheostatic starter> period of time during which the starting resistors or parts of them carry current
Note 1 to entry: The starting time of a starter is shorter than the total starting time of the motor which also takes into account the last period of acceleration following the switching operation to the ON position.
3.5.21
starting time
<auto-transformer starter> period of time during which the auto-transformer carries current
Note 1 to entry: The starting time of a starter is shorter than the total starting time of the motor which also takes into account the last period of acceleration following the switching operation to the ON position.
3.5.22
open transition
<with an auto-transformer starter or star-delta starter> circuit arrangement such that the supply to the motor is interrupted and reconnected when changing over from one step to another
Note 1 to entry: The transition stage is not considered as an additional step.
3.5.23
closed transition
<with an auto-transformer starter or star-delta starter> circuit arrangement such that the supply to the motor is not interrupted (even momentarily) when changing over from one step to another
Note 1 to entry: The transition stage is not considered as an additional step.
3.5.24
inching
jogging
energizing a motor or solenoid repeatedly for short periods to obtain small movements of the driven mechanism
3.5.25
plugging
stopping or reversing a motor rapidly by reversing the motor primary connections while the motor is running
3.5.26
protected switching device
equipment (for non-motor loads) consisting of a contactor or a semiconductor controller, overload protection, a manually operated switching device and a short-circuit protective device, rated as a unit by the manufacturer
Note 1 to entry: The protected switching device can be enclosed.
Note 2 to entry: In the context of this document, the term "manufacturer" means any person, company or organization with ultimate responsibility as follows:
-
to verify compliance with the appropriate standard;
-
to provide the equipment information according to Clause 6.
Note 3 to entry: The manually operated switching device and the short-circuit protective device can be just one device and can incorporate the overload protection as well.
3.5.27
combination switching device
equipment consisting of a protected switching device incorporating an isolating function
3.5.28
stall relay
stall release
electronic overload relay or release which operates when the current has not decreased below a predetermined value for a specific period of time during start-up or when the relay or the release receives the input indicating there is no rotation of the motor after a predetermined time in accordance with specified requirements
Note 1 to entry: Explanation of stall: rotor locked during start.
Note 2 to entry: With appropriate adjustment of the current and starting time settings, such relay or release can be used to detect starts requiring longer than specified times.
3.5.29
jam relay
jam release
electronic overload relay or release which operates in the case of overload and also when the current has increased above a predetermined value for a specific period of time during operation, in accordance with specified requirements
Note 1 to entry: A jam is a high overload occurring after the completion of starting which causes the current to reach the locked rotor current value of the motor being controlled.
3.5.30
inhibit time
time-delay period during which the tripping function of the relay is inhibited
3.5.31
motor management starter
starter including extended functions with communication ability
Note 1 to entry: Interoperable device profiles for motor management starter are defined by IEC 61915-2:2011.
3.5.32
motor protective switching device
MPSD
manually operated motor starter additionally providing resettable short-circuit protection to the motor and the circuit
Note 1 to entry: A MPSD can also be used as a manual starter, a protected starter or a combination starter.
Note 2 to entry: A MPSD can be used as a SCPD within the motor branch.
Note 3 to entry: In North America, this device can be qualified as a manual motor controller suitable for tap conductor protection.
3.5.33
instantaneous only motor protective switching device
IMPSD
motor protective switching device (MPSD) without overload protection function
Note 1 to entry: This type of device is typically used in a 3 components starter where the overload protection function is within a separately mounted overload relay.
3.5.34
dedicated wiring accessory
prefabricated connection wiring system specifically intended for identified switchgear or controlgear
Note 1 to entry: A dedicated wiring accessory can be integrated in the switchgear or controlgear or delivered separately.
Note 2 to entry: A typical dedicated wiring accessory is for example a connection link.
3.5.35
latch accessory
mechanical device attached to a contactor, the moving elements of which are prevented from returning to the position of rest when the operating means are de-energized
Note 1 to entry: The latching, and the release of the latching, can be mechanical, electromagnetic, pneumatic, etc.
[SOURCE: IEC 60050-441:1984, 441-14-34, modified - Adapted to accessories, and Note 2 to entry deleted]
3.5.36
basic drive module
BDM
electronic power converter and related control, connected between an electric supply and a motor
Note 1 to entry: The BDM is capable of transmitting power from the electric supply to the motor and may be capable of transmitting power from the motor to the electric supply.
Note 2 to entry: The BDM controls some or all of the following aspects of power transmitted to the motor and motor output: current, frequency, voltage, speed, torque, force.
[SOURCE: IEC 61800-5-1:2022, 3.6]

3.6Terms and definitions concerning characteristic quantities

3.6.1
product documentation
manufacturer's installation and operations' literature which accompanies the product, the product information contained in the manufacturer's catalogue and other product marketing material-information and, the description, definitions, product literature and usage as presented in electronic format on the manufacturer's (or supplier's) website on the World Wide Web/Internet
[SOURCE: ISO/IEC 14762:2009, 3.1.13, modified - Replacement of two ";" by "," and "and,".]
3.6.2
transient recovery voltage
TRV
recovery voltage during the time in which it has a significant transient character
Note 1 to entry: In a vacuum contactor or vacuum starter, the highest transient recovery voltage can occur on another pole than the first pole to clear.
[SOURCE: IEC 60947-1:2020, 3.7.34, modified - Note 1 to entry has been modified and Note 2 to entry was deleted.]
3.6.3
CO operation
breaking of the circuit by the SCPD resulting from closing the circuit by the equipment under test
3.6.4
O operation
breaking of the circuit by the SCPD resulting from closing the circuit on the equipment under test which is in the closed position
Note 1 to entry: The SCPD is normally in the closed position prior closing the circuit; in some cases, the SCPD closes the circuit (see 9.3.4.2.2, item b)).
3.6.5
Icd current
current representing a fault current equal to or higher than the current corresponding to the crossover point of the mean value of the published curves representing the time-current characteristics of the overload relay and the SCPD respectively
3.6.6
crossover current
Ico
current corresponding to the crossover point of the mean or published curves representing the time-current characteristics of the overload relay and the SCPD respectively
Note 1 to entry: The mean curves are the curves corresponding to the average values calculated from the tolerances on the time-current characteristics of the overload relay.
3.6.7
time-current withstand characteristic capability of contactors or starters
locus of the currents a contactor or starter can withstand as a function of time
3.6.8
resetting time
time elapsed between a circuit-breaker tripping due to an overcurrent and subsequently reaching a condition where it can be reclosed
[SOURCE: IEC 60947-2:2016, 2.19, modified - Insertion of "or a starter" in definition.]
3.6.9
conventional prospective current "r"
specified value of prospective short-circuit current for which the switching device is tested under specified conditions
3.6.10
I2t characteristic
<circuit-breaker or MPSD> information (usually a curve) giving the maximum values of I2t related to break time as a function of prospective current (RMS symmetrical for AC) up to the maximum prospective current corresponding to the rated service short-circuit breaking capacity and associated voltage
[SOURCE: IEC 60947-2:2016, 2.18, modified - "or MPSD" inserted in context, “service” inserted in definition.]
3.6.11
rated instantaneous short-circuit current setting
Ii
rated value of the current causing the operation of a release without any intentional time-delay
[SOURCE: IEC 60947-2:2016, 2.20]
3.6.12
overload current setting
Ir
current setting of an adjustable overload release
[SOURCE: IEC 60947-2:2016, 2.21, modified - Note 1 to entry has been deleted]
3.6.13
galvanic opening
<circuit> prevention of electric conduction within an electric circuit intended to provide power and/or signals
Note 1 to entry: Galvanic opening can be provided e.g. by a switch or a contactor.
3.6.14
galvanic separation
prevention of electric conduction between two electric circuits intended to exchange power and/or signals
Note 1 to entry: Galvanic separation can be provided e.g. by an isolating transformer or an opto-coupler.
[SOURCE: IEC 60050-151:2001, 151-12-26]
3.6.15
recurring peak voltage
maximum peak value of periodic excursions of the voltage waveform resulting from distortions of an AC voltage or from AC components superimposed on a DC voltage
Note 1 to entry: Random overvoltages, for example due to occasional switching, are not considered to be recurring peak voltages.
[SOURCE: IEC 60050-442:2014, 442-09-15]
3.6.16
rated voltage pulse slope
dV/dt
maximum admissible value of the voltage slope dV/dt of a pulse, at the ambient air temperature at such a repetition frequency that no significant increase of temperature occurs
[SOURCE: IEC 60384-17:2019, 1.5.3.5, modified - Replacement of dU/dT with dV/dt, and replacement of “rated” with “ambient air”.]
3.6.17
critical load current
Icrit
value of breaking current, within the range of service conditions, at which the arcing time is significantly extended
Note 1 to entry: This phenomenon, crucial for PV applications, is due to the low magnetic field coming from the arc current, creating a slow moving arc.
[SOURCE: IEC 60947-1:2020, 3.7.16, modified - In Note 1 to entry, replacement of “crucial for direct currents (e.g. photovoltaïc (PV) applications)” with “crucial for PV applications”.]
3.6.18
rated conventional switching current
Iscl
rated current assigned to a contactor for switching the current controlled to a low level by a semiconductor, taking into the account the rated operational voltage, the rated frequency and the rated duty
Note 1 to entry: This current is typically lower than Ie.

3.7Terms and definitions concerning safety aspects

3.7.1
abnormal operating condition
temporary operating condition that is not a normal operating condition and is not a single fault condition of the equipment itself
Note 1 to entry: An abnormal operating condition is a temporary condition which can be introduced by the equipment or by a person and can result in a failure of a component, a device or a safeguard.
Note 2 to entry: This definition is used in the context of component failure risk analysis.
3.7.2
accessible part
part which can be touched by means of the standard test finger
[SOURCE: IEC 60050-442:1998, 442-01-15]
3.7.3
live-part
conductive part intended to be energized in normal conditions, including a neutral conductor or mid-point conductor, but by convention not a PEN conductor or PEM conductor or PEL conductor
Note 1 to entry: This concept does not necessarily imply a risk of electric shock.
[SOURCE: IEC 60050-195:2021, 195-02-19, modified - Addition of a Note 1 to entry.]
3.7.4
hazardous-live-part
live part which, under certain conditions, can give a harmful electric shock
[SOURCE: IEC 60050-195:2021, 195-06-05 modified - Note 1 to entry deleted.]
3.7.5
limited energy source
source that is designed and protected that, under both normal operating conditions and single fault conditions, the current that can be delivered is not hazardous with respect to fire hazard
3.7.6
protective impedance
impedance connected between hazardous-live-parts and accessible conductive parts, of such value that the current, in normal use and under likely fault conditions, is limited to a safe value, and which is so constructed that its ability is maintained throughout the life of the equipment
[SOURCE: IEC 62477-1:2022, 3.60, modified - Replacement of “the PECS” with “the equipment”.]
3.7.7
reasonably foreseeable misuse
use of a product or system in a way not intended by the supplier, but which can result from readily predictable human behaviour
[SOURCE: ISO/IEC Guide 51:2014, 3.7, modified - Notes to entry have been removed.]
3.7.8
single fault condition
condition in which there is a fault of a single protection (but not a reinforced protection) or of a single component or a device
Note 1 to entry: If a single fault condition results in one or more other fault conditions, all are considered as one single fault condition.
[SOURCE: IEC Guide 104:2019, 3.8, modified - Deletion of Note 2 to entry.]
3.7.9
touch current
electric current passing through a human body or through an animal body when it touches one or more accessible parts of an electrical installation or electrical equipment
[SOURCE: IEC 60050-826:2022, 826-11-12, modified - Replacement of “livestock” with “animal body”, and addition of “electrical” (2 occurrences)]
3.7.10
hot functional surface
surface that is intentionally heated by an internal heat source and that has to be hot to carry out the function for which the equipment is intended to be used
[SOURCE: IEC Guide 117:2010, 3.5, modified - NOTE 1 and NOTE 2 have been deleted.]
3.7.11
mirror contact
normally closed auxiliary contact which cannot be in closed position simultaneously with the normally open main contact under conditions defined in Clause F.7
Note 1 to entry: One contactor can have more than one mirror contact.
3.7.12
safe state
state of the safety device which leads to a safe condition of the EUC
Note 1 to entry: In this annex, the safe state is the condition of the interruption of the motor load circuit.
3.7.13
hardware fault tolerance
HFT
ability of a safety device to continue to perform a required function in the presence of faults
3.7.14
SIL-capability
characteristic of functional units that comply with the requirements of IEC 61508-2 and IEC 61508-3 suitable for use in functions which are allocated a SIL 1, 2 or 3 respectively
[SOURCE: IEC 60079-29-3:2014, 3.15]
3.7.15
systematic failure
failure, related in a deterministic way to a certain cause, which can only be eliminated by a modification of the design or of the manufacturing process, operational procedures, documentation or other relevant factors
Note 1 to entry: Corrective maintenance without modification will usually not eliminate the failure cause.
Note 2 to entry: A systematic failure can be induced by simulating the failure cause.
Note 3 to entry: Examples of causes of systematic failures include human error in:
-
the safety requirements specification;
-
the design, manufacture, installation, operation of the hardware.
[SOURCE: IEC 61508-4:2010, 3.6.6, modified - Third example of Note 3 and Note 4 deleted]
3.7.16
safety integrity level
SIL
discrete level (one out of a possible four), corresponding to a range of safety integrity values, where safety integrity level 4 has the highest level of safety integrity and safety integrity level 1 has the lowest
[SOURCE: IEC 61508-4:2010, 3.5.8, modified - Notes to entry deleted]
3.7.17
risk priority number
RPN
one of the methods of quantitative determination of criticality
[SOURCE: derived from IEC 60812:2018, Annex B]

3.8Terms and definitions concerning electric motor characteristics

3.8.1
inrush current
first maximum value of current peak during motor start (positive or negative)
3.8.2
locked-rotor current
ILRC
greatest steady state rms current taken from the line with the motor held at rest, over all angular positions of its rotor, at rated voltage and frequency
Note 1 to entry: In the USA, ILRC DOL current is called LRA (Locked Rotor Amps).
Note 2 to entry: IEC 60034-1 provides a tolerance of 20 % of locked rotor direct-on-line current.
3.8.3
kappa factor
K
ratio of the root-mean-square value of the inrush current to the direct on-line current
Note 1 to entry: A typical value for high efficiency motors is 1,8.
3.8.4
motor rated current
rated current from the motor name plate
Note 1 to entry: In the USA, motor rated current is called FLA (Full Load Amps).

3.9Symbols and abbreviated terms

AQL
Acceptable quality level
EMC
Electromagnetic compatibility
EUC
Equipment under control
FMEA
Failure mode effect analysis
FRU
Field replaceable unit
FTA
Fault tree analysis
HFT
Hardware Fault Tolerance
MPSD
Motor protective switching device
RPN
Risk priority number
SCPD
Short-circuit protective device
SIL
Safety integrity level
Î
Maximum peak value of the pick-up current of an electronically controlled electromagnet
Ic
Current made and broken (Table 7)
Icd
Maximum crossover breaking current (B.4.5)
Ics
Rated service short-circuit breaking capacity (5.3.6.2)
Icu
Rated ultimate short-circuit breaking capacity (5.3.6.1)
Ie
Rated operational current (5.3.2.5)
Ier
Rated rotor operational current (5.3.2.7)
Ies
Rated stator operational current (5.3.2.6)
Ii
Instantaneous short-circuit current setting
IIT
Short-circuit test current for IT system
Iq
Maximum conditional short-circuit test current
Ir
Overload current setting
Ith
Conventional free air thermal current (5.3.2.1)
Ithe
Conventional enclosed thermal current (5.3.2.2)
Ithr
Conventional rotor thermal current (5.3.2.4)
Iths
Conventional stator thermal current (5.3.2.3)
Iu
Rated uninterrupted current (5.3.2.8)
Pc
Nominal holding or pickup power of a conventional direct current controlled electromagnet, or the holding power for an electronically direct current controlled electromagnet
Pp
Pick-up power of a direct current controlled contactor with separate pick-up and hold-on windings
"r"
conventional prospective current
Sh
Holding power of an alternating current controlled electromagnet
Sp
Pick-up power of an alternating current controlled electromagnet
Tp
Tripping time (Table 2)
Uc
Rated control circuit voltage (5.5)
Ud
Voltage drop of a contactor pole
Ue
Rated operational voltage (5.3.1.1)
Uer
Rated rotor operational voltage (5.3.1.1.3)
Ues
Rated stator operational voltage (5.3.1.1.2)
Ui
Rated insulation voltage (5.3.1.2)
Uimp
Rated impulse (withstand) voltage (5.3.1.3)
Uir
Rated rotor insulation voltage (5.3.1.2.3)
Uis
Rated stator insulation voltage (5.3.1.2.2)
Ur
Power frequency or DC recovery voltage (Table 7)
Us
Rated control circuit supply voltage (5.5)
Uv
Maximum continuous operating voltage of the varistor
U0
Rated supply voltage
Z
Pole impedance of a contactor (5.3.7)
30mm
20mm
15mm
15mm
10mm
17mm

Gulf StandardGSO IEC 60947-4-1:2024
Gulf StandardGSO IEC 60947-4-1:2024
Gulf StandardGSO IEC 60947-4-1:2024
GSO IEC 60947-4-1:2024Gulf Standard
Bibliography
IEC 60050-151, International Electrotechnical Vocabulary (IEV) - Part 151: Electrical and magnetic devices
IEC 60050-195, International Electrotechnical Vocabulary (IEV) - Part 195: Earthing and protection against electric shock
IEC 60050-421, International Electrotechnical Vocabulary (IEV) - Part 421: Power transformers and reactors
IEC 60050-441, International Electrotechnical Vocabulary (IEV) - Part 441: Switchgear, controlgear and fuses
IEC 60050-442, International Electrotechnical Vocabulary (IEV) - Part 442: Electrical accessories
IEC 60050-826, International Electrotechnical Vocabulary (IEV) - Part 826: Electrical installations
IEC 60068-2-2:2007, Environmental testing - Part 2-2: Tests - Test B: Dry heat
IEC 60072-1:2022, Rotating electrical machines - Dimensions and output series - Part 1: Frame numbers 56 to 400 and flange numbers 55 to 1080
IEC 60079 (all parts), Explosive atmospheres
IEC 60079-7, Explosive atmospheres - Part 7: Equipment protection by increased safety "e"
IEC 60079-29-3:2014, Explosive atmospheres - Part 29-3: Gas detectors - Guidance on functional safety of fixed gas detection systems
IEC 60204-1, Safety of machinery - Electrical equipment of machines - Part 1: General requirements
IEC 60269-1:2006, Low-voltage fuses - Part 1: General requirements
IEC 60269-2:2013, Low-voltage fuses - Part 2: Supplementary requirements for fuses for use by authorized persons (fuses mainly for industrial application) - Examples of standardized systems of fuses A to K
IEC 60364-7-712, Low voltage electrical installations - Part 7-712: Requirements for special installations or locations - Solar photovoltaic (PV) power supply systems
IEC 60384-17:2019, Fixed capacitors for use in electronic equipment - Part 17: Sectional specification - Fixed metallized polypropylene film dielectric AC and pulse capacitors
IEC 60417 Graphical symbols for use on equipment, available at http://www.graphical-symbols.info/equipment
IEC 60664-1:2020, Insulation coordination for equipment within low-voltage supply systems -Part 1: Principles, requirements and tests
IEC 60721-3-3, Classification of environmental conditions - Part 3-3: Classification of groups of environmental parameters and their severities - Stationary use at weatherprotected locations
IEC 60812:2018, Failure modes and effects analysis (FMEA and FMECA)
IEC 60947-3:2020, Low-voltage switchgear and controlgear - Part 3: Switches, disconnectors, switch-disconnectors and fuse-combination units
IEC 60947-4-2, Low-voltage switchgear and controlgear - Part 4-2: Contactors and motor-starters - Semiconductor motor controllers, starters and soft-starters
IEC 60947-6-2, Low-voltage switchgear and controlgear - Part 6-2: Multiple function equipment - Control and protective switching devices (or equipment) (CPS)
IEC 60947-8, Low-voltage switchgear and controlgear - Part 8: Control units for built-in thermal protection (PTC) for rotating electrical machines
IEC 60990:2016, Methods of measurement of touch current and protective conductor current
IEC 61000-6-5, Electromagnetic compatibility (EMC) - Part 6-5: Generic standards - Immunity for equipment used in power station and substation environment
IEC 61032, Protection of persons and equipment by enclosures - Probes for verification
IEC 61508-2, Functional safety of electrical/electronic/programmable electronic safety-related systems - Part 2: Requirements for electrical/electronic/programmable electronic safety-related systems(see http://www.iec.ch/functionalsafety)
IEC 61508-3, Functional safety of electrical/electronic/programmable electronic safety-related systems - Part 3: Software requirements(see http://www.iec.ch/functionalsafety)
IEC 61508-4:2010, Functional safety of electrical/electronic/programmable electronic safety-related systems - Part 4: Definitions and abbreviations(see http://www.iec.ch/functionalsafety)
IEC 61508-6:2010, Functional safety of electrical/electronic/programmable electronic safety-related systems - Part 6: Guidelines on the application of IEC 61508-2 and IEC 61508-3(see http://www.iec.ch/functionalsafety)
IEC 61557-12:2018, Electrical safety in low voltage distribution systems up to 1 000 V AC and 1 500 V DC - Equipment for testing, measuring or monitoring of protective measures - Part 12: Power metering and monitoring devices (PMD)
IEC 61557-12:2018/AMD1:2021
IEC 61649, Weibull analysis
IEC 61915-2:2011, Low-voltage switchgear and controlgear - Device profiles for networked industrial devices - Part 2: Root device profiles for starters and similar equipment
IEC 62061, Safety of machinery - Functional safety of safety-related control systems
IEC 62443 (all parts), Security for industrial automation and control systems
IEC 62477-1:2022, Safety requirements for power electronic converter systems and equipment - Part 1: General
IEC 62683-1, Low-voltage switchgear and controlgear - Product data and properties for information exchange - Part 1: Catalogue data
IEC 63365, Industrial process measurement, control and automation - Digital nameplate
IEC TR 63054, Low-voltage switchgear and controlgear - Fire risk analysis and risk reduction measures
IEC TR 63201:2019, Low-voltage switchgear and controlgear - Guidance for the development of embedded software
IEC 63404, 3 Switchgear and controlgear and their assemblies for low voltage - Integration method of radiocommunication device into an equipment
IEC Guide 104:2019, The preparation of safety publications and the use of basic safety publications and group safety publications
IEC Guide 117:2010, Electrotechnical equipment - Temperatures of touchable hot surfaces
ISO/IEC 80079-34, Explosive atmospheres - Part 34: Application of quality systems for ex product manufacture
ISO/IEC 14762:2009, Information technology - Functional safety requirements for Home and Building Electronic Systems (HBES)
ISO/IEEE 82079-1:2012, Preparation of instructions for use - Structuring, content and presentation - Part 1: General principles and detailed requirements4
ISO/IEC Guide 51:2014, Safety aspects - Guidelines for their inclusion in standards
ISO 3534-2:2006, Statistics - Vocabulary and symbols - Part 2: Applied statistics
JIS C 4213: 2014, Low-voltage three-phase squirrel-cage induction motors - Low-voltage top runner motor
CSA C22.1, Canadian Electrical Code
CLC/TR 45550:2020, Definitions related to material efficiency
EN 45556, General method for assessing the proportion of reused components in energy-related products
EN 50495, Safety devices required for the safe functioning of equipment with respect to explosion risks
NFPA 70, National Electrical Code
PROFIEnergy profile test specification V1.1:2014
UL 508:2021, Industrial control equipment
UL 60947-1, Low-Voltage Switchgear and Controlgear - Part 1: General rules
UL 60947-4-1, Low-voltage switchgear and controlgear - Part 4-1: Contactors and motor-starters - Electromechanical contactors and motor-starters
30mm
20mm
15mm
15mm
10mm
17mm
INTERNATIONALELECTROTECHNICALCOMMISSION3, rue de VarembéPO Box 131CH-1211 Geneva 20SwitzerlandTel: +41 22 919 02 11info@iec.chwww.iec.ch

3Under preparation. Stage at the time of publication: IEC FDIS 63404:2023.
4This publication was withdrawn and replaced with IEC/IEEE 82079-1:2019.